DCA-60SSI2 — GENERATOR SHUT-DOWN PROCEDURE

DCA-60SSI2 — GENERATOR SHUT-DOWN PROCEDURE

ENGINE SHUTDOWN

To shutdown the generator, use the following procedure:

1.Switch both the MAIN, GFCI and LOAD circuit breakers (Figure 55)to the “OFF” position.

EMERGENCY STOP

1.To stop the engine in the event of an emergency, switch the MAIN, GFCI and LOAD circuit breakers to ‘OFF’ position.

2.Turn the key switch to ‘STOP’.

Figure 55. Main, GFCI and Load circuit breakers

2.Turn to the right and press in the engine throttle lever (Figure 56).

Figure 56. Engine Throttle Lever

3.Let the engine cool by running it for 3-5 minutes with no load applied.

4.Turn the key switch to ‘STOP’’ (Figure 57).

Figure 57. Key Switch (OFF)

5. Remove the load from the UVW terminal strip.