Multiquip DCA-60SS12 DCA-60SSI2— GENERATOR START-UPPROCEDURE, abnormal condition occurs

Models: DCA-60SS12

1 164
Download 164 pages 7.84 Kb
Page 49
Image 49
abnormal condition occurs.

DCA-60SSI2 — GENERATOR START-UP PROCEDURE

15.The charging ammeter (Figure 51) will indicate if the battery is properly charged.

Figure 47. Voltage Adjust Control

Figure 51. Charging Ammeter

Knob

 

12.The ammeter (Figure 48) will indicate zero amps with no load applied. When a load is applied, this meter will indicate the amount of current that the load is drawing from the generator’s alternator.

16.The tachometer (Figure 52) will indicate the speed of the engine when the generator is operating. Under normal operating conditions this speed is approximately 1800 RPM’s.

40

2060

0

75

A

Figure 52. Engine Tachometer

Figure 48. Ammeter (No Load)

13.The engine oil pressure gauge (Figure 49) will indicate the oil pressure (kg/ cm2) of the engine. Under normal operating conditions the oil pressure is approximately 25 psi.

Figure 49. Oil Pressure Gauge

14.The coolant temperature gauge (Figure 50) will indicate the coolant temperature. Under normal operating conditions the coolant temperature is between 165 and 215 degrees fahrenheit.

17.Turn the MAIN, GFCI and LOAD circuit breakers to their ON position (Figure 53).

Figure 53. Main and GFCI Circuit Breakers

18.Observe the generator's ammeter (Figure 54) and verify it reads the anticipated amount of current with respect to the load. The ammeter will only display a current reading if the load is in use.

40

2060

0

75

A

WATER TEMP

Figure 54. Ammeter (Load)

19. The generator will run until manually stopped or an

Figure 50. Coolant Temperature Gauge

abnormal condition occurs.

 

 

DCA-60SSI2 — PARTS AND OPERATION MANUAL— REV. #3 (09/15/01) — PAGE 49

 

 

Page 49
Image 49
Multiquip DCA-60SS12 operation manual DCA-60SSI2— GENERATOR START-UPPROCEDURE, abnormal condition occurs