DCA-60SSIU — OUTPUT AMPERAGE SETUP
Output Terminal Panel Available Voltages
A wide range of voltages are available to supply load to many different applications. Voltages may be selected by using the voltage selector switch and depending how you hookup your hard wire connection to the generator. To obtain some of the voltages listed, fine adjustment with the voltage regulator on the control panel is necessary. See Table 8 for available voltages the generator will supply.
Over Current Relay
An over current relay is connected to the circuit breaker. During an over current situation, both the circuit breaker and the over current relay will trip. If the circuit breaker can not be reset, the reset button on the over current relay must be pressed. The over current relay is located inside the control box.
Table 8. Voltage Available
3 Phase | 208 VOLT | 220 VOLT | 240 VOLT | 416 VOLT | 440 VOLT | 480 VOLT | |
(Switchable) | |||||||
|
|
|
|
|
| ||
|
|
|
|
|
|
| |
Single Phase | 120 VOLT | 127 VOLT | 139 VOLT | 240 VOLT | 254 VOLT | 277 VOLT | |
(Switchable) | |||||||
|
|
|
|
|
| ||
|
|
|
|
|
|
|
CAUTION :
NEVER switch Voltage Selector Switch position while the engine is engaged.
Maximum Amps
Table 9 shows the maximum amps the generator will pro- vide. Do not exceed the maximum amps listed.
Voltage Selector Switch Locking Button
The voltage selector switch has a locking button to protect the generator and generator load from being switched while the engine is running. To lock the voltage selector switch, press in the red button located on the voltage selector switch, and use a pad lock to hold it into this position.
Table 9. Maximum Amps
Rated | Maximum Amps | |
Voltage | ||
| ||
|
| |
Single Phase | 133.3 amps (4 wire) | |
120 Volt | ||
| ||
|
| |
Single Phase | 66.7 amps (4 wire) | |
240 Volt | ||
| ||
|
| |
Three Phase | 144 amps | |
240 Volt | ||
| ||
|
| |
Three Phase | 72 amps | |
480 Volt | ||
| ||
|
|
PAGE 34 —