– 111 –
Super Digital Inverter
How to open the valve
Open or close the valve.
Liquid side
Open the valve with a 4 mm hexagon wrench.
Gas side
Valve unit
Using a minus screwdriver, turn it counterclockwise by 90° until it hits the stopper. (Full open)
Charge port
Flare nut
Handle position
Closed completely | Opened fully |
Stopper pin
Movable part of valve (Stem)
Main stopper
Replenishing refrigerant
This model is a 30 m chargeless type that does not need to have its refrigerant replenished for refrigerant pipes up to
30 m. When a refrigerant pipe longer than 30 m is used, add the specified amount of refrigerant.
Refrigerant replenishing procedure
1. After vacuuming the refrigerant pipe, close the valves and then charge the refrigerant while the air conditioner is not working.
2. When the refrigerant cannot be charged to the specified amount, charge the required amount of refrigerant from the charge port of the valve on the gas side during cooling.
Requirement for replenishing refrigerant
Replenish liquid refrigerant.
When gaseous refrigerant is replenished, the refrigerant composition varies, which disables normal operation.
Adding additional refrigerant
31~75 m: L
40 g ×
•L: Pipe length
•To add additional refrigerant to twin and triple systems, refer to the installation manual supplied with the branching pipe (sold separately).
•The refrigerant need not be reduced for a 30 meter (or less) refrigerant pipe.
Super Digital Inverter
7 ELECTRICAL WORK
WARNING
1. Using the specified wires, ensure that the wires are connected, and fix wires securely so that the external tension to the wires does not affect the connecting part of the terminals.
Incomplete connection or fixation may cause a fire, etc.
2.Be sure to connect the earth wire. (grounding work) Incomplete grounding may lead to electric shock. Do not connect ground wires to gas pipes, water pipes, lightning rods or ground wires for telephone wires.
3.The appliance shall be installed in accordance with national wiring regulations.
Capacity shortages of the power circuit or an incomplete installation may cause an electric shock or fire.
CAUTION
•Wrong wiring may cause a
•Be sure to use the cord clamps attached to the product.
•Do not damage or scratch the conductive core or inner insulator of the power and
•Use the power and
•Remove the panel, and you can see electric parts on the front side.
•A metal pipe can be installed through the hole for wiring. If the hole size does not fit the wiring pipe to be used, drill the hole again to an appropriate size.
•Be sure to clamp the power wires and indoor/outdoor connecting wires with a banding band along the
connecting pipe so that the wires do not touch the compressor or discharge pipe.
(The compressor and the discharge pipe become hot.) Furthermore, be sure to secure these wires with the pipe valve fixing plate and cord clamps stored in the electric parts box.
Electric parts box
Panel
Pipe valve fixing plate
Cord clamp
Pipe hole
•While the valve is fully opened, after the screwdriver has reached the stopper, do not apply torque exceeding
5 N•m. Applying excessive torque may damage the valve.
Valve handling precautions
•Open the valve stem until it strikes the stopper. It is unnecessary to apply further force.
•Securely tighten the cap with a torque wrench.
Cap tightening torque
| Ø9.5 mm | 33 to 42 N•m |
| (3.3 to 4.2 kgf•m) | |
Valve size |
| |
|
| |
| Ø15.9 mm | 20 to 25 N•m |
| (2.0 to 2.5 kgf•m) | |
|
| |
|
|
|
Charge port |
| 14 to 18 N•m |
| (1.4 to 1.8 kgf•m) | |
|
| |
|
|
|
Wiring between Indoor Unit and Outdoor Unit
The dashed lines show on-site wiring.
| Outdoor unit | Indoor unit | ||
| L1 |
| Wired remote controller | |
| 1 | 1 | ||
| L2 | |||
Input power | 2 | 2 | ||
L3 | ||||
3 | 3 | |||
N | ||||
|
|
|
Leakage breaker
•Connect the indoor/outdoor connecting wires to the identical terminal numbers on the terminal block of each unit. Incorrect connection may cause a failure.
For the air conditioner, connect a power wire with the following specifications.
Model | 110AT8 | 140AT8 | 160AT8 |
|
|
|
|
Power supply |
|
| |
| 50 Hz |
| |
|
|
| |
|
|
|
|
Maximum running current |
| 16.4 A |
|
|
|
|
|
Recommended field fuse |
| 20 A |
|
|
|
|
|
Power wire* |
| 5 ⋅ 2.5 mm2 or more |
|
| (H07 |
| |
|
|
| |
|
|
|
|
Indoor/outdoor connecting wires* |
| 4 ⋅ 1.5 mm2 or more |
|
| (H07 |
| |
|
|
| |
|
|
|
|
* Number of wire wire size |
|
|
|
20 | 21 |