Error mode detected by indoor unit

Error mode detected by indoor unit

 

Operation of diagnostic function

 

 

 

 

 

 

Judgment and measures

Check

Cause of operation

Status of

Condition

 

code

air conditioner

 

 

 

 

 

 

 

 

 

 

No communication from remote

Stop

Displayed when

1. Check cables of remote controller and communication adapters.

 

• Remote controller LCD display OFF (Disconnection)

E03

controller (including wireless) and

(Automatic reset)

error is detected

 

communication adapter

• Central remote controller [97] check code

 

 

 

 

 

 

 

 

 

 

 

 

 

The serial signal is not output from

 

 

1. Outdoor unit does not completely operate.

 

outdoor unit to indoor unit.

 

 

Inter-unit wire check, correction of miswiring

 

• Miswiring of inter-unit wire

 

 

 

Stop

Displayed when

• Check outdoor P.C. board. Correct wiring of P.C. board.

E04

• Defective serial sending circuit on

(Automatic reset)

error is detected

2. When outdoor unit normally operates

 

 

outdoor P.C. board

 

 

Check P.C. board (Indoor receiving / Outdoor sending).

Defective serial receiving circuit on indoor P.C. board

E08

Duplicated indoor unit address

 

 

1.

Check whether remote controller connection (Group/Individual)

 

 

 

 

 

was changed or not after power supply turned on

 

 

 

 

 

L03

Duplicated indoor master unit

 

Displayed when

 

(Finish of group construction/Address check).

 

 

Stop

 

* If group construction and address are not normal when the

 

 

 

L07

There is group wire in individual indoor

error is detected

 

power has been turned on, the mode automatically shifts to

 

 

unit.

 

 

 

address setup mode. (Resetting of address)

 

 

 

 

 

 

 

 

 

 

L08

Unset indoor group address

 

 

 

 

 

 

 

 

 

L09

Unset indoor capacity

Stop

Displayed when

1. Set indoor capacity (CODE No. (DN) = 11)

error is detected

 

 

 

 

 

 

 

 

 

 

 

 

L30

Abnormal input of outside interlock

Stop

Displayed when

1. Check outside devices.

error is detected

2.

Check indoor P.C. board.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Float switch operation

 

 

1.

Trouble of drain pump

P10

Stop

Displayed when

2. Clogging of drain pump

• Float circuit, Disconnection,

error is detected

3.

Check float switch.

 

 

 

Coming-off, Float switch contact error

 

 

 

 

 

4.

Check indoor P.C. board.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.

Position detection error

P12

Indoor DC fan error

Stop

Displayed when

2. Over-current protective circuit of indoor fan driving unit operated.

error is detected

3.

Indoor fan locked.

 

 

 

 

 

 

 

 

 

 

 

4.

Check indoor P.C. board.

 

 

 

 

 

 

 

4-way valve system error

 

 

1.

Check 4-way valve.

 

Stop

Displayed when

2. Check 2-way valve and check valve.

P19

• After heating operation has started,

(Automatic reset)

error is detected

3.

Check indoor heat exchanger (TC/TCJ).

 

indoor heat exchangers temp. is

 

 

 

 

down.

 

 

4.

Check indoor P.C. board.

 

 

 

 

 

 

P31

Own unit stops while warning is output

Stop

Displayed when

1.

Judge follower unit while header unit is [E03], [L03], [L07] or [L08].

(Follower unit)

2.

Check indoor P.C. board.

to other indoor units.

error is detected

 

(Automatic reset)

 

 

 

 

 

 

 

 

 

F01

Coming-off, disconnection or short of

Stop

Displayed when

1.

Check indoor heat exchanger temp. sensor (TCJ).

indoor heat exchanger temp. sensor

2. Check indoor P.C. board.

(Automatic reset)

error is detected

 

(TCJ)

 

 

 

 

 

 

 

 

 

 

 

F02

Coming-off, disconnection or short of

Stop

Displayed when

1.

Check indoor heat exchanger temp. sensor (TC).

indoor heat exchanger temp. sensor

2. Check indoor P.C. board.

(Automatic reset)

error is detected

 

(TC)

 

 

 

 

 

 

 

 

 

 

 

F10

Coming-off, disconnection or short of

Stop

Displayed when

1.

Check indoor heat exchanger temp. sensor (TA).

indoor heat exchanger temp. sensor

2. Check indoor P.C. board.

(Automatic reset)

error is detected

 

(TA)

 

 

 

 

 

 

 

 

 

 

F29

Indoor EEPROM error

Stop

Displayed when

1. Check indoor EEPROM. (including socket insertion)

• EEPROM access error

(Automatic reset)

error is detected

2.

Check indoor P.C. board.

 

 

 

 

 

 

 

 

 

 

 

Communication error between indoor

Stop

 

1.

Check indoor P.C. board.

E10

MCU

Displayed when

 

 

• Communication error between fan

(Automatic reset)

error is detected

 

 

 

 

 

 

 

 

 

 

 

driving MCU and main MCU

 

 

 

 

 

 

 

 

 

 

 

Regular communication error between

Stop

Displayed when

1.

Check remote controller wiring.

 

 

 

E18

indoor aster and follower units and

2.

Check indoor power supply wiring.

(Automatic reset)

error is detected

 

between main and sub units

3.

Check indoor P.C. board.

 

 

 

 

 

 

 

– 65 –