Toshiba RAV-SP1404AT8-E 108, Refrigerant Piping, Installation of Outdoor Unit, For Reference

Models: RAV-SP1404AT8Z-E RAV-SP1104AT8Z-E RAV-SP1404AT8ZG-E RAV-SP1404AT8-E RAV-SP1604AT8-TR RAV-SP1104AT8Z-TR RAV-SP1604AT8-E RAV-SP1404AT8-TR RAV-SP1604AT8Z-E RAV-SP1104AT8ZG-E RAV-SP1404AT8Z-TR RAV-SP1404AT8ZG-TR RAV-SP1104AT8-TR RAV-SP1104AT8ZG-TR

1 143
Download 143 pages 52.35 Kb
Page 108
Image 108
￿Installation of Outdoor Unit

Super Digital Inverter

Serial installation in front and rear

Open above and to the right and left of the unit.

The height of an obstacle in both the front and rear of the unit should be lower than the height of the outdoor unit.

Standard installation

1,000 or

300 or

1,500 or

2,000 or

200 or

more

more

more

more

more

￿Installation of Outdoor Unit

Before installation, check the strength and horizontalness of the base so that abnormal sounds do not emanate.

According to the following base diagram, fix the base firmly with the anchor bolts.

(Anchor bolt, nut: M10 x 4 pairs)

As shown in the figure below, install the foundation and vibration-proof rubber pads to directly support the bottom surface of the fixing leg that is in contact with and

underneath the bottom plate of the outdoor unit.

*When installing the foundation for an outdoor unit with downward piping, consider the piping work.

GOOD

Absorb vibration

Fixing legwith vibration-proof

rubber pads

Foundation ￿For Reference

GOOD

Bottom plate of

outdoor unit

Foundation – 108 –5 REFRIGERANT PIPING￿Knockout of Pipe CoverEN-14

Support the bottom surface of the

Super Digital Inverter

When water is to be drained through the drain hose, attach the following drain nipple and waterproof rubber cap, and use the drain hose (Inner diam: 16 mm) sold on the market. Also seal knockout hole and the screws securely with silicone material, etc., to prevent water from leaking.

Some conditions may cause dewing or dripping of water.

When collectively draining discharged water completely, use a drain pan.

Waterproof rubber cap

Drain nipple

￿For Reference

If a heating operation is to be continuously performed for a long time under the condition that the outdoor temperature is

0°C or lower, draining defrosted water may be difficult due to the bottom plate freezing, resulting in trouble with the cabinet or fan.

It is recommended to procure an anti-freeze heater locally in order to safely install the air conditioner.

For details, contact the dealer.

– 108 –

400

 

Drain hole

 

 

525

 

150

600

150

 

45

 

365

Drain hole

Drain nipple

mounting hole

fixing leg that is in contact with and underneath the bottom plate of the outdoor unit.

NO GOOD

If only the end of the

Do not support the

fixing leg is supported, it

outdoor unit only with

may deform.

the fixing leg.

 

Foundation 15-ENManual background

Set the out margin of the anchor bolt to 15 mm or less.

15 or less

Drain nipple

Waterproof rubber cap

Knockout hole

5 REFRIGERANT PIPING

￿Knockout of Pipe Cover

Knockout procedure

Rear direction

Pipe cover

Side direction

Front direction

Down direction

The indoor/outdoor connecting pipes can be connected in 4 directions.

Take off the knockout part of the pipe cover through which pipes or wires will pass through the base plate.

Detach the pipe cover and tap on the knockout section a few times with the shank of a screwdriver. A knockout hole can easily be punched.

After punching out the knockout hole, remove burrs from the hole and then install the supplied protective bush and guard material around the passage hole to protect wires and pipes.

Be sure to attach the pipe covers after pipes have been connected. Cut the slits under the pipe covers to facilitate the installation.

After connecting the pipes, be sure to mount the pipe cover. The pipe cover is easily mounted by cutting off the slit at the lower part of the pipe cover.

*Be sure to wear heavy work gloves while working.

EN-14

14

15

15-EN
Page 108
Image 108
Toshiba RAV-SP1404AT8-E 108, Refrigerant Piping, Installation of Outdoor Unit, For Reference, Knockout of Pipe Cover