GENERAL7DATA

NOMINAL 3 TONS

Model

TGC036C-1K-120

TGC036C-3K-120

TGC036C-4K-120

Cooling Performance1

 

 

 

Gross Cooling Capacity Btuh

37400

37400

37400

EER/SEER2

11.7/13

11.7/13

11.7/13

Nominal CFM/ARI Rated CFM

1200/1200

1200/1200

1200/1200

ARI Net Cooling Capacity Btuh

36000

36000

36000

Net Sensible Capacity Btuh

26400

26400

26400

Net Latent Capacity Btuh

9600

9600

9600

Net System Power kW

3.08

3.08

3.08

Heating Performance (Package Gas/Electric) 3

 

 

Heating Input Btuh

120000

120000

120000

Heating Output Btuh

94500

97200

97200

Temperature Rise ºF

50-80

50-80

50-80

AFUE (%)

80

80

80

Steady State Efficiency (%)

81

81

81

Qty of Burners

6

6

6

Qty of Stages

1

1

1

Gas Connection Pipe Size, in.

.5

.5

.5

Compressor

 

1/Copeland Scroll

 

Qty/Type

 

 

Outdoor Sound Rating (dB)

78

78

78

Outdoor Coil—Fin Type

 

Louvered

 

Tube Type

Rifled

Rifled

Rifled

Tube Size in. OD

0.375

0.375

0.375

Face Area sq. ft.

16.91

16.91

16.91

Rows / Fins per inch

1/22

1/22

1/22

Indoor Coil—Fin Type

 

Corrugated

 

Tube Type

Rifled

Rifled

Rifled

Tube Size in.

0.375

0.375

0.375

Face Area sq. ft.

5.17

5.17

5.17

Rows / Fins per inch

2/17

2/17

2/17

Refrigerant Control

TXV

TXV

TXV

Drain Connection Qty/Size, in.

1/0.75

1/0.75

1/0.75

Outdoor Fan—Type

 

Propeller

 

Qty Used/Diameter in.

1/24

1/24

1/24

Drive Type/Speeds

Direct/1

Direct/1

Direct/1

CFM

3680

3680

3680

Qty Motors-HP

1-1/3

1-1/3

1-1/3

Motor RPM

1075

1075

1075

Indoor Fan—Type

 

Forward Curved Centrifugal

 

Qty Used/Diameter in.

1/10x10

1/10x10

1/10x10

Drive Type/Speeds

Direct/3

Direct/3

Direct/3

Motor Qty

1

1

1

Motor HP

1/2

1/2

1/2

Motor RPM

1075

1075

1075

Motor Frame Size

48

48

48

Filter—Type

 

Disposable

 

Furnished

Yes

Yes

Yes

(Qty) Size Recommended in.

(2)16x25x1

(2)16x25x1

(2)16x25x1

Refrigerant Charge Oz.

93

93

93

Weights

 

 

 

Net Weight lbs.

543

543

543

Ship Weight lbs.

550

550

550

Notes: 1. Cooling performance is rated at 95ºF ambient, 80ºF/67ºF entering dry bulb/wet bulb temperatures. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to plus or minus 20% of nominal cfm. Units are certified and rated per ARI Standard 210/240.

2.EER/SEER are rated ARI condition and accordance with DOE test procedures.

3.Heating performance limit settings and rating data were established and approved under laboratory test conditions using American National Standard Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, rating should be resuced 4% for each 1000 feet above sea level.

Heat Controller, Inc. -7-

Page 7