SELECTION6PROCEDURE EXAMPLE

SELECTION6PROCEDURE EXAMPLE

1.Determine cooling and heating requirements at design conditions. Example:

Total cooling capacity

43,600 BTUH

Sensible cooling capacity

34,000 BTUH

Heating capacity

96,000 BTUH

Condenser entering air

95°F

Evaporator entering air

63°F wbt/76°F dbt

Indoor air flow

1600 CFM

External static pressure

0.6 in wg

Required efficiency

13 SEER

2.Select unit to meet cooling requirements.

Since total cooling is within the range of 4 ton unit and

requires 13 SEER efficiency level, enter cooling performance from the TGC048C at 95°F outdoor temperature, 63°F wbt

entering indoor air, and 1550 CFM:

Total capacity

....................................47,300 BTUH

Power input

3.5 kW

And also, at 76°F db indoor entering air, and using the formula

at the bottom of the table:

 

Sensible capacity

41,708 BTUH

3.Select heating capacity of the unit.

In the general data tables, note that the heating capacity of the 4 ton model with the 135,000 input heater can deliver 106,500

BTUH, which is suitable for this application.

4.Determine blower speed and power to meet the system

requirements.

At the given external static pressure of 0.6 in wg, the belt model must be selected. Enter the belt drive blower performance data at 1580 CFM and 0.6 in wg ESP:

Watts........635

5.Calculate indoor blower BTUH heat effect.

BTUH = Watts x 3.413 = 2168

6. Calculate net cooling capacities.

Net total cooling = 47,300 – 2168 = 45,132 BTUH

Net sensible cooling = 41,708 – 2168 = 39,540 BTUH