GENERAL9DATA
NOMINAL 4 TONS
Model | |||
Cooling Performance1 |
|
|
|
Gross Cooling Capacity Btuh | 49000 | 49000 | 49000 |
EER/SEER2 | 11.4/13.1 | 11.4/13.1 | 11.4/13.1 |
Nominal CFM/ARI Rated CFM | 1600/1550 | 1600/1550 | 1600/1550 |
ARI Net Cooling Capacity Btuh | 47000 | 47000 | 47000 |
Net Sensible Capacity Btuh | 33600 | 33600 | 33600 |
Net Latent Capacity Btuh | 13400 | 13400 | 13400 |
Net System Power kW | 4.15 | 4.15 | 4.15 |
Heating Performance (Package Gas/Electric) 3 |
|
| |
Heating Input Btuh | 135000 | 135000 | 135000 |
Heating Output Btuh | 106500 | 109400 | 109400 |
Temperature Rise ºF | |||
AFUE (%) | 80 | 80 | 80 |
Steady State Efficiency (%) | 81 | 81 | 81 |
Qty of Burners | 6 | 6 | 6 |
Qty of Stages | 1 | 1 | 1 |
Gas Connection Pipe Size, in. | .5 | .5 | .5 |
Compressor |
| 1/Copeland Scroll |
|
Qty/Type |
|
| |
Outdoor Sound Rating (dB) | 78 | 78 | 78 |
Outdoor |
| Louvered |
|
Tube Type | Rifled | Rifled | Rifled |
Tube Size in. OD | 0.375 | 0.375 | 0.375 |
Face Area sq. ft. | 16.56 | 16.56 | 16.56 |
Rows / Fins per inch | 2/22 | 2/22 | 2/22 |
Indoor |
| Corrugated |
|
Tube Type | Rifled | Rifled | Rifled |
Tube Size in. | 0.375 | 0.375 | 0.375 |
Face Area sq. ft. | 5.17 | 5.17 | 5.17 |
Rows / Fins per inch | 3/15 | 3/15 | 3/15 |
Refrigerant Control | TXV | TXV | TXV |
Drain Connection Qty/Size, in. | 1/0.75 | 1/0.75 | 1/0.75 |
Outdoor |
| Propeller |
|
Qty Used/Diameter in. | 1/24 | 1/24 | 1/24 |
Drive Type/Speeds | Direct/1 | Direct/1 | Direct/1 |
CFM | 3680 | 3680 | 3680 |
Qty | |||
Motor RPM | 1075 | 1075 | 1075 |
Indoor |
| Forward Curved Centrifugal |
|
Qty Used/Diameter in. | 1/10x10 | 1/10x10 | 1/10x10 |
Drive Type/Speeds | Direct/3 | Direct/3 | Direct/3 |
Motor Qty | 1 | 1 | 1 |
Motor HP | 1/2 | 1/2 | 1/2 |
Motor RPM | 1075 | 1075 | 1075 |
Motor Frame Size | 48 | 48 | 48 |
| Disposable |
| |
Furnished | Yes | Yes | Yes |
(Qty) Size Recommended in. | (2)16x25x1 | (2)16x25x1 | (2)16x25x1 |
Refrigerant Charge Oz. | 167 | 167 | 167 |
Weights |
|
|
|
Net Weight lbs. | 585 | 585 | 585 |
Ship Weight lbs. | 592 | 592 | 592 |
Notes: 1. Cooling performance is rated at 95ºF ambient, 80ºF/67ºF entering dry bulb/wet bulb temperatures. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to plus or minus 20% of nominal cfm. Units are certified and rated per ARI Standard 210/240.
2.EER/SEER are rated ARI condition and accordance with DOE test procedures.
3.Heating performance limit settings and rating data were established and approved under laboratory test conditions using American National Standard Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, rating should be resuced 4% for each 1000 feet above sea level.
Heat Controller, Inc.