Heatcraft Refrigeration Products CC-CUBZTB manual Electrical Data, Number, Evap, Mop††, Volts

Models: CC-CUBZTB

1 24
Download 24 pages 37.7 Kb
Page 15
Image 15
Evap.

Electrical Data

Medium & Low Temperature – R-404A/R-507

 

 

Compressor

Condenser Fan

Beacon II™ or

 

Remote Loads

 

 

 

Motors

Air Defrost

 

 

Unit Model

Compressor

 

 

 

Electric Defrost

 

 

 

 

 

 

 

 

 

 

Number

Model

RLA

LRA

Qty.

 

FLA

MCA

MOP††

Evap.

Defrost

System

System

 

 

 

 

 

 

 

 

 

Fan

Heaters

MCA

MOP††

 

 

 

 

 

 

 

 

 

Amps

Amps

 

 

 

 

 

208-230 Volts

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CDV*150BM6

4C2067PH

48.7

294

2

 

9.6

70.5

110

 

 

 

 

CDV*200BM6

4C2397PH

57.7

352

2

 

14.0

86.1

125

 

 

 

 

CDV*220BM6

4B2707PH

61.5

352

2

 

14.0

90.9

150

 

 

 

 

CDV*250BM6

4B3139PH

75.6

436

2

 

14.0

108.5

175

 

 

 

 

CDV*300BM6

4B3604PH

89.7

490

3

 

21.0

133.1

200

 

 

 

 

CDV*330BM6

6B4060PH

100.0

550

3

 

21.0

146.0

225

 

 

 

 

CDV*350BM6

6B4709PH

105.1

550

3

 

21.0

152.4

250

CONTACT FACTORY FOR SYSTEM

CDV*400BM6

6B5406PH

141.0

700

4

 

28.0

204.3

325

CDV*500BM6

6B6462PH

143.6

950

4

 

28.0

207.5

350

 

ELECTRICAL RATINGS

 

CDV*130BL6

4B2707PL

43.6

294

2

 

9.6

64.1

100

 

 

 

 

CDV*150BL6

4B3139PL

46.2

294

2

 

9.6

67.4

110

 

 

 

 

CDV*200BL6

4B3604PL

57.7

352

2

 

9.6

81.7

125

 

 

 

 

CDV*220BL6

6B4060PL

65.4

436

2

 

14.0

95.8

150

 

 

 

 

CDV*250BL6

6B4709PL

69.2

436

2

 

14.0

100.5

150

 

 

 

 

CDV*300BL6

6B5406PL

84.6

490

2

 

14.0

119.8

200

 

 

 

 

CDV*400BL6

6B6462PL

97.4

700

3

 

21.0

142.8

225

 

 

 

 

 

 

 

 

 

460 Volts

 

 

 

 

 

 

CDV*150BM6

4C2067PH

24.4

147

2

 

4.8

35.3

60

 

 

 

 

CDV*200BM6

4C2397PH

28.8

176

2

 

7.0

43.0

70

 

 

 

 

CDV*220BM6

4B2707PH

30.8

176

2

 

7.0

45.5

70

 

 

 

 

CDV*250BM6

4B3139PH

37.8

218

2

 

7.0

54.3

90

 

 

 

 

CDV*300BM6

4B3604PH

44.9

245

3

 

10.5

66.6

110

 

 

 

 

CDV*330BM6

6B4060PH

50.0

275

3

 

10.5

73.0

110

 

 

 

 

CDV*350BM6

6B4709PH

52.6

275

3

 

10.5

76.3

125

CONTACT FACTORY FOR SYSTEM

CDV*400BM6

6B5406PH

70.5

350

4

 

14.0

102.1

150

CDV*500BM6

6B6462PH

71.8

425

4

 

14.0

103.8

175

 

ELECTRICAL RATINGS

 

CDV*130BL6

4B2707PL

21.8

147

2

 

4.8

32.1

50

 

 

 

 

CDV*150BL6

4B3139PL

23.1

147

2

 

4.8

33.7

50

 

 

 

 

CDV*200BL6

4B3604PL

28.8

176

2

 

4.8

40.8

70

 

 

 

 

CDV*220BL6

6B4060PL

32.7

218

2

 

7.0

47.9

80

 

 

 

 

CDV*250BL6

6B4709PL

34.6

218

2

 

7.0

50.3

80

 

 

 

 

CDV*300BL6

6B5406PL

42.3

245

2

 

7.0

59.9

100

 

 

 

 

CDV*400BL6

6B6462PL

48.7

350

3

 

10.5

71.4

110

 

 

 

 

 

 

 

 

 

575 Volts

 

 

 

 

 

 

CDV*150BM6

4C2067PH

19.6

117

2

 

4.6

29.1

40

 

 

 

 

CDV*200BM6

4C2397PH

23.6

140

2

 

5.6

35.1

50

 

 

 

 

CDV*220BM6

4B2707PH

24.4

140

2

 

5.6

36.1

60

 

 

 

 

CDV*250BM6

4B3139PH

30.1

165

2

 

5.6

43.2

70

 

 

 

 

CDV*300BM6

4B3604PH

35.9

196

3

 

8.4

53.3

80

 

 

 

 

CDV*330BM6

6B4060PH

39.7

220

3

 

8.4

58.0

90

 

 

 

 

CDV*350BM6

6B4709PH

41.7

220

3

 

8.4

60.5

100

CONTACT FACTORY FOR SYSTEM

CDV*400BM6

6B5406PH

56.4

280

4

 

11.2

81.7

125

CDV*500BM6

6B6462PH

57.1

340

4

 

11.2

82.6

125

 

ELECTRICAL RATINGS

 

CDV*130BL6

4B2707PL

17.3

117

2

 

4.6

26.2

40

 

 

 

 

CDV*150BL6

4B3139PL

18.6

117

2

 

4.6

27.9

45

 

 

 

 

CDV*200BL6

4B3604PL

23.1

140

2

 

4.6

33.5

50

 

 

 

 

CDV*220BL6

6B4060PL

26.9

174

2

 

5.6

38.5

60

 

 

 

 

CDV*250BL6

6B4709PL

27.6

174

2

 

5.6

40.1

60

 

 

 

 

CDV*300BL6

6B5406PL

33.3

196

2

 

5.6

47.2

80

 

 

 

 

CDV*400BL6

6B6462PL

39.1

280

3

 

8.4

57.3

90

 

 

 

 

CDV* = CDVS is Beacon II

MCA = Minimum Circuit Ampacity

† MOP = Maximum Overcurrent Protection

‡ Condensing unit data plate ratings will be based on actual system match.

Beacon IIand Air Defrost Units do not carry any of the evaporator fan or heater loads. Power is brought directly to the evaporators and does not go through the condensing unit.

An evaporator heater hold out relay (option) is recommended when two or more evaporators are connected to a single (CDV) condensing unit to allow termination on coils that have already defrosted to prevent unnecessary steaming. This option is not needed on Beacon II(CDVS) systems wired for a Master / Slave operation. Power is brought to each Beacon evaporator. Each coil terminates its own defrost. Refrigeration will not start until all coils have terminated defrost.

Single Vertical Air Discharge Condensing Unit

15

Page 15
Image 15
Heatcraft Refrigeration Products CC-CUBZTB Electrical Data, Single Vertical Air Discharge Condensing Unit, Number, Evap