HEAD PRESSURE CONTROL
Refrigeration condensing units must efficiently | Operation | |||
perform at varying ambient conditions. A properly |
|
|
| |
sized unit will adequately perform at even the | As the ambient temperature falls, the system | |||
highest summer ambient temperatures. However, | condensing pressure is also reduced. This pressure | |||
in situations where the system must operate the | is maintained by a regulator | |||
majority of the time at less than design temperature, | condenser drain. At approximately 75°F saturated | |||
a means of providing adequate head pressure | condensing pressure the regulator restricts the flow | |||
for refrigerant flow is desirable. The CDV & CDD | of liquid refrigerant from the condenser causing the | |||
units have an adjustable method of head pressure | condenser to flood. This condenser flooding allows | |||
control. | the liquid refrigerant in the condenser to become | |||
| subcooled by the ambient air flowing through the | |||
This system provides year round control of refrigerant | condenser. As the regulator continues to flood the | |||
condenser, a pressure differential will be established | ||||
head pressure without the use of special refrigerant | ||||
between the receiver and the compressor discharge. | ||||
expansion valves. As the ambient temperature falls, | ||||
At a predescribed differential, a second valve (ORD- | ||||
the reciever pressure is allowed to fall to a minimum | ||||
4) will open and allow discharge gas from the | ||||
of 75°F saturated condensing pressure. The reduced | ||||
compressor to bypass the condenser and flow into | ||||
discharge pressure at the compressor increases the | ||||
the top of the receiver. This gas is used to pressurize | ||||
compressor capacity and lowers the input watts | ||||
the receiver. These valves are adjustable and the | ||||
from the compressor motor. The system also uses | ||||
minimum receiver pressure may be reset higher or | ||||
the reduced ambient temperature to subcool the | ||||
lower depending upon application situations of a | ||||
liquid refrigerant in the condenser. This subcooled | ||||
particular job. | ||||
liquid also increases system capacity. As a general | ||||
|
|
| ||
rule, every one degree of subcooling results in 0.50% | Subcooled liquid is further enhanced by the routing | |||
increase in system capacity. Together these result | ||||
|
|
| ||
in greater efficiency, greater capacity, and reduced of liquid from the receiver liquid line outlet to the | ||||
run time. | condenser before leaving the condensing unit. | |||
|
|
| ||
Benefits: |
|
|
| |
• Automatic |
|
|
| |
|
|
| ||
pressure without the use of special expansion |
|
|
| |
valves. |
|
|
| |
• Energy savings in mild ambient conditions due |
|
|
| |
to reduced compressor discharge pressure and |
|
|
| |
refrigerant subcooling |
|
|
| |
• Provides easy restart during low ambient |
|
|
| |
conditions. |
|
|
|
5