Heatcraft Refrigeration Products CC-CUBZTB Standard and Optional Features, Nomenclature, 000B

Models: CC-CUBZTB

1 24
Download 24 pages 37.7 Kb
Page 12
Image 12
Single Vertical Air Discharge Condensing Unit

Vertical Air Discharge Condensing Units 13 to 50 HP Single Compressor

Single Vertical Air Discharge Condensing Unit

Standard and Optional Features

The Floating Tube™ coil design. Refrigerant-carrying copper tubes do not contact any metal support sheets; instead, the coil is constructed with expanded anchor tubes that support the coil construction and do not carry refrigerant. The coil design eliminates one of the major causes of leaks in refrigeration systems

Limited five-year warranty against condenser tube sheet and center support leaks

Designed for use with R-404A, R-507

Prebent copper tubes minimize welded joints on internal piping

All sweat type connections, no flare joints to leak

Fixed high pressure switch eliminates capillary tubes

Oil safety control

Bitzer compressors with POE oil

Spring mounted compressor with suction and discharge vibration eliminators

Crankcase heater

Thermally protected, permanently lubricated ball bearing condenser fan motors

Separate subcooling circuit in condenser for added capacity and vapor-free liquid

Receivers are sized for sufficient pumpdown capacity with inlet and outlet service valves

Pressure relief valve on receiver

Sealed liquid line filter drier and sight glass

Electrical controls, including compressor contactor and optional defrost control, are located in easily accessible control box with a hinged cover

Service Matemodule to assist troubleshooting

Pumpdown Switch

Cabinet is constructed from prepainted galvanized steel

Convenient access panels for easy servicing to internal components

Adjustable head pressure control valves

Factory-Installed Options

Compressor unloading

Replaceable core liquid filter drier

Liquid line solenoid valve

Suction filter

Replaceable core suction filter

Suction accumulator

Oil separator with discharge line check valve

Air defrost timer

Electric defrost kits, including timer, evaporator fan contactor with fusing, defrost heater contactor(s), lockout relay and terminal strip

Fusing for defrost kits

Evaporator holdout relays for systems with multiple electric defrost evaporators

Low ambient kit with heated and insulated receiver with time delay

Fused disconnect switch

Non-fused disconnect switch

Phase-loss protection

Manual-reset high pressure switch

Anti-short cycle timer

Compressor circuit breakers

Condenser fan cycling (standard on CDVS)

Three-way heat reclaim valve (n/a on CDVS)

Coated condenser coils for protection against corrosion in harsh environments

Beacon IIcompatible

Nomenclature

C

D

V

000B

L

6

C

Brand

 

Airflow

Horsepower

Temp. Range

Refrigerant

Voltage

 

 

C=

Climate Control

D -

V = Vertical

VS = Vertical Beacon II

130B - 13

150B - 15

200B - 20

220B - 22

250B - 25

300B - 30

330B - 33

350B - 35

400B - 40

500B -50

M = Med. Temp.

L = Low Temp.

6 = R-404A,

R-507

C = 208-230/3/60 D = 460/3/60

E = 575/3/60

12

Page 12
Image 12
Heatcraft Refrigeration Products CC-CUBZTB Standard and Optional Features, Factory-InstalledOptions, Nomenclature, 000B