Head Pressure Setpoint
The head pressure setpoint potentiometer is adjustable from
Minimum Output
The minimum output potentiometer controls the minimum signal sent to the motor. .It is adjustable from
Throttling range
The throttling range potentiometer controls how far the system pressure must deviate from the control setpoint to generate a 100% output signal from the control. .It is adjustable from
Integration constant
The integration constant switch provides ability to change controller from a proportional only control to a proportional plus integral control..To provide the most responsive system to maintain a stable head pressure, it is recommended this setting be left on “fast..”
Reverse acting or direct acting mode of operation
The reverse acting/direct acting jumper is used to ensure the controller responds correctly to maintain desired head pressure. .In Direct Acting (DA) mode, the motor speed increases as the pressure rises above desired setpoint. .For proper condenser operation, this jumper MUST be in Direct Acting (DA) mode. .Failure to ensure J1 jumper is in direct acting mode will cause the system to trip on high head pressure..
See Diagram #4 for typical proportional pressure control wiring..
Motor RPM | Motor RPM |
Chart 1. .Ramp characteristics with 200 psig setpoint and 50 psig throttling range
Chart 2. .Ramp characteristics with 200 psig setpoint and 100 psig throttling range