Henny Penny 322, 324, 323 kPa 34.5 mbar, Gas Supply, Continued, Do not use cast iron fittings

Models: 323 322 324

1 11
Download 11 pages 59.25 Kb
Page 4
Image 4
(Continued)

 

Model OFE/OFG-321,322,323,324

2-6. GAS SUPPLY

The fryer and its manual shutoff valve must be disconnected

(Continued)

from the gas supply piping system during any pressure

 

testing of that system at test pressures in excess of ½ PSIG

(3.45 kPa) (34.5 mbar).

The fryer must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than ½ PSIG (3.45 kPa) (34.5 mbar).

A standard one inch (2.54 cm), black steel pipe and malleable fittings should be used for gas service connections for 3 well open fryers, 3/4 inch (1.91 cm) for 2 wells, and 1/2 inch (1.27 cm) for single wells.

Do not use cast iron fittings.

Although one inch (2.54 cm) size pipe is recommended for

3 wells, 3/4 inch (1.91 cm) for 2 wells, and 1/2 inch (1.27 cm) for single wells, piping should be of adequate size and installed to provide a supply of gas sufficient to meet the maximum demand without undue loss of pressure between the meter and the open fryer. The pressure loss in the piping system should not exceed 0.3 in. water column (0.747 mbar).

Provisions should be made for moving the open fryer for cleaning and servicing. This may be accomplished by:

1.Installing a manual gas shut off valve and a disconnect union, or

2.Installing a heavy-duty design A.G.A. certified connector. In order to be able to service this appliance, which is provided with casters, a connector complying with ANSI Z21.69 or CAN 1-6.l0m88 and a quick-disconnect device, complying with ANSI Z21.41 or CAN 1-6.9m70, must be installed. It must also be installed with restraining means to guard against transmission of strain to the connector as specified in the appliance manufacturer's instruction.

3.See the illustration on the following page for the proper connection of flexible gas line and cable restraint.

The cable restraint limits the distance the open fryer can be pulled from the wall. For cleaning and servicing the unit, the cable must be unsnapped from the open fryer and the flexible gas line disconnected. This will allow better access to all sides of the open fryer. The gas line and cable restraint must be reconnected once the cleaning or servicing is complete.

703

2-4

Page 4
Image 4
Henny Penny 322, 324, 323 installation instructions kPa 34.5 mbar, Gas Supply, Continued, Do not use cast iron fittings