Hill Phoenix 05DMA manual Control Settings, Johnson Controls, To Initiate Manual Defrost

Models: 05DMA

1 32
Download 32 pages 40.02 Kb
Page 16
Image 16
To Initiate Manual Defrost:

CONTROL SETTINGS

Johnson Controls

 

Error Code

System Status

 

 

 

F1

Indicates an open or

Alarm output on compressor

 

shorted temperature

runs according to the sensor

 

sensor. Cycle Power

failure mode selected (para-

 

to reset control.

meter sf)

 

 

 

F2

Indicates an open or

Alarm output on defrost

 

shorted evaporator

cycle is controlled by para-

 

sensor. Correct

meters di (defrost initiation)

 

problem to reset

and dd (defrost duration)

 

control.

 

 

 

 

A1

Digital input was open

Compressor off

 

for longer than time

Alarm output on

 

delay (id) and digital

 

 

input option (if) 1 is

 

 

selected.

 

 

 

 

A2

Digital input is closed

Alarm output is on

 

and digital input option

 

 

(if) 1 is selected.

 

 

 

 

A3

Digital input is open

Fan output is off

 

for longer than time

Alarm output is on

 

delay (id) and digital

 

 

input option (if) 3 is

 

 

selected.

 

 

 

 

HI

Temperature has

Alarm output is on

 

exceeded the high

 

 

temp. alarm value (AH).

 

 

 

 

LO

Temperature has fallen

Alarm output is on

 

below the low temp.

 

 

alarm value (AL).

 

 

 

 

EE

Program failure: control

Alarm output is on

 

must be replaced.

Other outputs off

 

 

 

To Initiate Manual Defrost:

Hold the Defrost button down for 3 seconds.

To program parameters:

1. Hold the “Enter” button down for about 10 seconds. The display will change to “Hy.”

2. Press the “Up” and “Down” button until the desired parameter is shown

3. Press the “Enter” button. The para- meter’s current value will be shown.

4. Press the “Up” and “Down” button until the desired value is shown.

5. Press the “Enter” button to save the new value. After 10 seconds of inactivi- ty, the display will return to its normal function.

To change setpoint:

1. Hold down the “Enter” button down for 3 seconds. The display will change to show the setpoint.

2. Press the “Up” or “Down” button until you reach the new setpoint.

3. Press the “Enter” button to save the new setpoint.

To lock and unlock the unit:

}

Press the “Enter,” the “Up,” and the

“Down” buttons in sequence and hold

them all down until “- - -” is displayed.

Hold for about 10 seconds until the

current temperature is displayed.

To Initiate a deep freeze cycle:

Press and the “Enter” and “Up” buttons To program parameters:} in sequence and hold for five seconds.

The compressor status LED will light.

To Initiate Self-Test:

IMPORTANT: Disconnect loads before To change setpoint:} beginning self test. Cycle power to

resume operation.

Press the “Up” and the “Down” buttons in sequence and hold for 5 seconds.

12

Page 16
Image 16
Hill Phoenix 05DMA manual Control Settings, Johnson Controls, To Initiate Manual Defrost, To program parameters