User Level Setpoints - O5DMA

Code

Parameter Name

Min

Max

Units

O5DMA

 

Setpoint

 

 

°C/°F

38

PS

Password

0

199

 

22

/C

Offset for air temp sensor

-127

127

°C/°F

0

 

(in tenths of a degree: i.e. a value of “1” adds 0.1° to value)

 

 

 

 

rd

Regulator differential (superheat) set point (a “0” in this field = 0.5°C or 0.5°F)

0

19

°C/°F

3

dI

Time between defrost cycles (defrost interval)

0

199

hours

6

dt

Defrost temperature termination set point

-50

127

°C/°F

44

dP

Max duration of defrost if using electric or hot gas defrost, or the actual

1

199

min

42

 

duration of defrost if doing timed defrost

 

 

 

 

dd

Drip time

0

15

min

0

d8

Alarm delay after defrost

0

15

hours

1

d/

Defrost probe reading (read-only)

 

 

°C/°F

 

AL

Low temperature alarm differential (subtract this value from the temperature

0

127

°C/°F

-10

 

set point to get low alarm temperature set point) (0 = no low temp alarming)

 

 

 

 

AH

High temperature alarm differential (add this value to the temperature set

0

127

°C/°F

20

 

point to get high alarm temperature set point) (0 = no high temp alarming)

 

 

 

 

F1

Fan on at temperature set point (used if F0 = 1)

-50

199

°C/°F

5

Fd

Fan delay after defrost drip time for each F0 value

0

15

min

1

H5

ID code for programming key

-99

+

 

8

T

External parameter programming

-99

199

 

 

15

Page 19
Image 19
Hill Phoenix 05DMA manual User Level Setpoints O5DMA