CONTROL SETTINGS
ESC3 Controls
Alarm Operation
Indications on the Display
If the defrost, or compressor key blinks, it means that the corresponding function is delayed by a timing routine or inhibited. Other
Viewing and Changing the Temperature Setpoint The temperature setpoint is the comparison point for the control temperature input. To change the set point value:
1. Press the Alarm key for more than 5 seconds until the |
setpoint is displayed and blinking. |
Table 1
Code | Meaning |
E0 | Air probe has failed |
E1 | Defrost termination or product probe has failed |
LO | Low temperature alarm |
HI | High temperature alarm |
Ed | Defrost timeout has occurred |
| (did not terminate correctly) |
dF | Case is in defrost (not an alarm) |
|
|
ESC3 Case Controller
Compressor Key
2. | Press the Compressor key and Defrost keys to |
| raise/lower the value. |
3. | Press the Alarm key again to accept the new value. |
Changing Other Setpoints
There are two levels of setpoints in the ESC3. The first level does not require a password to change (unless the buttons are locked out). The setpoints that can be changed in this manner are identified in Table 1 (back side) as a USER setpoint. All other setpoint do require a password to change and are identified in Table 2 (back side) as an OEM setpoint. To change
Defrost Key
Alarm Key
1.Press the Alarm key and hold it until the letters PS are displayed.
2.Use the Compressor and Defrost key to scroll through the codes for the different set points (see Table 1 and Table 2).
3.When the code is displayed for the setpoint you wish to change, press the Alarm key. The value for that setpoint will be displayed.
4.Press the Compressor or Defrost key to change the value
5.Press the Alarm key to go back to the code.
At this point you must press the Alarm key to accept the change or press the Compressor or Defrost key to scroll to the next USER setpoint. To accept the changes, press and hold the Alarm key until the display stops flashing. To change
|
| K1 | R1 |
|
|
| |
J4 | J6 | J5 | |
120Vac Neutral | Fan Compressor | 120V Hot Defrost | Amb temp Common Def temp |
5 | 6 |
| K2 |
4 | 1 |
|
|
Control Input | 0.39 A, 120 Vac, 60 Hz |
Common Input | 11.2 A, 120 Vac, 60 Hz |
Fan Output | 1 FLA, 6 LRA, 120 Vac, 60 Hz |
Compressor Output | 1.5 HP @ 120 Vac |
(K2) | (external relay |
| by Song Chuan) |
Defrost Output | 10.0 A, 120 Vac, Resistive, 60 Hz |
| (P/N |
14