Hitachi J300 manual Contents Display, Display Function Standard Setting Set Value

Models: J300

1 6
Download 6 pages 59.56 Kb
Page 3
Image 3

HITACHI INVERTER

J300 SERIES

QUICK REFERENCE GUIDE (Part 1/2)

Three phase input 400V

FUNC. [FUNC key] ... This key switches between the parameter area, data

area, and extended function area.

Each time the key is pressed, the display changes as follows:

F 6

FUNC

30.1

30.0

FUNC

F 6

After the data has been changed, press the FUNC key to save data.

Protective Functions

The SJ100 series inverter will trip on overcurrent, overvoltage and undervoltage to protect the inverter.The output is shut down and the motor runs free. This condition is held until it is reset.

Trip

Contents

Display

Overcurrent

When the output of the inverter is short circuited,

Const. speed:E 1/ 31

protection

the motor is locked, or a heavy load is suddenly

At decelerat.:E 2/ 32

 

applied, and the inverter output current exceeds a

At accelerat.:E 3/ 33

 

predetermined level, the inverter is shut off.

 

At the others:E 4/ 34

 

 

29.9

[UP key, DOWN key] ... These keys change the values of data area, and parameters:

Overload

When a motor overload is detected by the electronic

E 5

 

protection

thermal function, the inverter is shut off.

 

 

Braking resis-

When regenerative braking resistor exceeds the usage

E 6

 

tor overload

time duration an overvoltage caused by the stop of the

 

 

 

BRD function is detected, and inverter output is cut off.

 

the on.

Overvoltage

When the inverter DC bus voltage exceeds a pre-

E 7

FUNC-Taste

This key is used to select parameters and for storing modified parameters.

RUN Key

This key is used for starting using the direction set by F 4. (When terminal run is selected this key does not function).

Monitor (LED-Display)

This display shows frequency, motor current, voltage, motor direction, and other parameters.

POW ER

FUNC.

R U N

$%!￿#￿$￿%

STOP/RESET key This key is used for stopping the motor or resetting errors or trips.

Power Lamp

Power Lamp of Control Circuit

UP/+ Key, DOWN/- Key

These keys are used to change data and parameters.

d 0

Output frequency

F 4

Set the motor

monitor

direction

d 1

Motor revolution

F 6

Set acceleration

monitor

time

d 2

Output current

F 7

Set deceleration

monitor

time

d 3

Scaled output

F 8

Manual boost

frequency monitor

configuration

d10

Trip monitor

F 9

Control mode

configuration

d11

Trip history

F10

FM signal

monitor

adjustment

F 2

Output frequency

F11

Motor voltage

monitor / setting

AVR function

 

 

F14

Extended

 

 

functions

protection

determined level due to regenerative energy from the

 

sure to observe ist value. If power is turned off while

the EEPROM error occurs when power is turnedback

 

motor, this trip occures and the inverter is shut off.

 

EEPROM error When the inverter memory has a problem due to

E 8

(NOTE 1)

noise or excessive temperature rise, this trip occurs

 

 

and the inverter is shut off.

 

Undervoltage

A decrease of DC bus voltage may result in improper

E 9

protection

function of the control unit. It may also cause motor

 

 

heating and low torque. The inverter is shut off when

 

 

the DC bus voltage goes below a certain level.

 

CT error

When a large noise source is near the inverter or an

E10

 

abnormality occurs on built-in CT, inverter output is

 

 

cut off.

 

CPU error

Malfunction or abnormality of the CPU. The inverter

E1 1

 

is shut off.

 

External trip

A trip signal from external equipment shuts off the

E12

 

inverter. It is necessary to assign the external trip to

 

 

an intelligent terminal.

 

USP error

Indicates an error when power is turned on while the

E13

 

inverter run is enabled (with USP function selected).

 

EEPROM error occurs, be

input terminal is held ON,

Ground fault

The inverter is protected by detection of ground

E14

protection

faults between the drive output and the motor at

 

 

power on. Protection is for the inverter only and not

 

 

for humans.

 

Input

When the input voltage is higher than a specified

E15

overvoltage

value, it is detected and 100 seconds after power is

 

 

turned on, the inverter is shut off.

 

Short power

A short input voltage interruption (>15ms) occured.

 

Operation procedure (example for the digital operator)

000

FUNC.

d 0

F 4

FUNC.

r

 

 

 

 

 

 

 

(7 x)

 

 

 

Turn power

 

 

 

 

 

 

on.

 

If reverse run (r ) is on, forward

 

 

 

 

run (F ) can be selected using

 

F

 

 

 

the UP or DOWN key.

 

 

 

 

 

 

 

 

FUNC

Data is

 

 

 

 

 

stored

 

 

 

 

 

 

[START key] ... This key

[STOP key] ... This key

starts the J300 inverter.

stops the J300 inverter.

RUN

$%!￿#￿$￿%

Set forward or reverse

When a trip occurs, this key

run using F 4.

becomes the RESET key

Setting extended functions

down

The inverter is shut off.

 

If an [RS]

Error in link to

There is an error in the link to the extension card in

Slot 1: E17

1:

option 1

slot 1 (2). The inverter is shut off.

Slot 2: E18

NOTE

(option 2)

 

 

Error option 1

There is an error in the extension card in slot 1 (2).

Slot 1: E19

(option 2)

The inverter is shut off.

Slot 2: E20

 

Phase failure

One of the power supply phases has broken down.

E24

 

 

The inverter is shut off.

 

 

Starting command and set value via

F 4

digital operator (instead of terminals)

 

 

 

Data is

 

 

 

(4 x)

 

 

stored

 

(3 x)

 

 

F 9

FUNC.

00

03

FUNC.

F 9

(5 x)

 

 

 

 

 

Data is

 

 

 

 

 

 

F

2

 

0.0

60.0

 

stored

FUNC

FUNC

 

 

 

 

 

 

 

 

Press con-

 

 

FUNC.

F14

FUNC.

Extended functions are entered from F14 using the FUNC key. Following this, the function parameter number is displayed for which data had been entered last.

 

Extended function

A 0

parameter number

 

When an extended function is to be used, select the

 

extended function group F14 by using the two

A 1

keys

and

so as to enter the extended

 

function mode.

 

Extended function data.

J300 data setting values

J300 inverters provide many functions whose parameters can be

set by the user. It is recommended that the parameters that have been set by the user be recorded in order to speed the

investigation and re-

J300

This information is written on

pair in the event of

 

the nameplate located on one of

a failure.

Mfg.No.

the sides of the J300 inverter.

 

Drive keypad display sequence

 

 

Display

Function

Standard Setting

Set Value

d 0 .. d 3 Display functions

Refer to page 4

d10, d11

 

 

 

tinuously

 

Setting frequency to 60Hz

Start run

RUN

 

(Motor operates)

 

F 2

Monitoring actual

(6 x)

output frequency

 

60.0

FUNC

d 0

After changes to data

 

 

 

200

have been made, the

A96

FUNC .

0

FUNC key must be

 

 

 

 

pressed. When the

 

FUNC .

 

 

FUNC key is being

 

 

 

 

 

 

 

pressed once more,

Return to extended

 

 

control is returned back

function parameter

 

 

to A - -.

and memorize

 

 

Explanation of display at power on

When the inverter is turned on, the display returns to what was displayed when the power was last turned off (except in the extended function mode).

 

 

 

 

 

 

 

 

F 2

Set output frequency (Hz)

0.0

 

F 4

Set motor direction

F (forward)

 

F 6

Acceleration time (s)

30.0

 

F 7

Deceleration time (s)

30.0

 

F 8

Configure manual boost

31

 

F 9

Configure control mode

03

 

F10

FM signal adjustment

72

 

F11

Motor voltage AVR function

380

 

F14

Extended function group

Refer to pages 6 and 7

3

4

5

Page 3
Image 3
Hitachi J300 manual Contents Display, Display Function Standard Setting Set Value