OM-478 Page 26
120V AC
6-3. Optional 5 kVA/kW Power Plant Receptacles
1 240 V 13 A AC Duplex
Receptacle RC1
2 120 V 15 A AC GFCI
Receptacle GFCI2
RC1 and GFCI2 supply 60 Hz sing-
le-phase power at weld/power
speed.
3 Circuit Breaker CB1 And CB2
CB1 and CB2 protect RC1 from
overload. CB2 also protects GFCI2
from overload. If CB1 or CB2 open,
the respective receptacle(s) does
not work. Press button to reset
breaker.
If a circuit breaker continues to
open, contact Factory Autho-
rized Service Agent.
4 Total Auxiliary Power Output
Combined output of RC1 and
GFCI2 is limited to 3 kVA/kW output
of the generator.
EXAMPLE: If 10 A is drawn from
GFCI2, only 7.5 A is available at
RC1:
(120 V x 10 A) + (240 V x 7.5 A) =
3.0 kVA/kW
5 240 Volts AC Three-Phase
Power Receptacle RC4
RC4 supplies 240 V, 12 A, 60 Hz
three-phase power at weld/power
speed. Maximum output from RC4
is 5 kVA/kW.
6 Circuit Breaker CB5
CB5 protects RC4 from overload. If
CB5 opens, the receptacle does
not work. Press button to reset
breaker.

240 VOLTS AC

THREE PHASE POWER

Ref. ST-150 972 / Ref. ST-174 757
6
5