REMOTE SETBACK SWITCH
The thermostat can be connected to a remote switch to toggle the desired heat and cool temperature settings between preset setpoints. A signal can be sent from the remote switch location to change the thermostat temperature settings from the Occupancy Day temperature settings to the Occupancy Night temperature settings. To use this mode, the “Program Options” setting must be set to “Occupancy” - See Program Options.
Run a
ANY SYSTEM WITH | THERMOSTAT | |
A RELAY OR | UP | |
5 - 15 VDC OUTPUT | ||
|
Leave Jumper
Connected
Black |
Green |
5 -15
VDC
Figure 12 – Connections to a Remote Setback Switch
Notes:
1.When connecting to a remote setback switch, the metal jumper between terminal labeled “N/C” and the terminal labeled “Black” on the right terminal strip must remain in place – See Figure 12.
2.When 0VDC is applied, the desired temperature settings will change to the preset Occupancy Day temperature settings.
3.When
OTHER SYSTEMS
For connections to personal computers, utility management systems, and other automation systems, refer to connection diagrams provided with personal computer software package or other system.
13