About Heat Pump Systems
1)Terminal 5 (O) is energized for cooling Terminal 6 (B) is energized for heating
In most applications, the reversing valve is energized for cooling and should be connected to the "O" terminal. If the heat pump requires the reversing valve to be energized for heating, connect the reversing valve to the "B" terminal.
2)With a call for Stage 2 on a two speed heat pump, both compressor outputs Y1 and Y2 are energized. When 2 stages of cooling and 2 stages of heating are configured for a heat pump, Stage 2 is considered high speed on the heat pump and not auxiliary heat. If auxiliary heat (or emergency heat) in needed, configure 3 stages of heating on the heat pump.
3)To temporarily disable Energy Efficient Control and heat as quickly as possible, press [HOLD] and select “On”. The
4)Terminal 9 (L) is used to indicate a fault with the heat pump compressor. When there is a compressor fault, the display will flash red and the “Heat Pump Fault” error message is shown.
5)The Emergency Heat Relay (E Terminal) and outdoor thermostats (usually accessories to a heat pump), are not used. The
About Dual Fuel Heat Pump Systems
A dual fuel heat pump typically has a gas furnace combined with a heat pump. The gas furnace is used as auxiliary heat unless the outdoor temperature is very low, in which case it is used as the primary heat source.
1)When used with dual fuel heat pumps, the
If the
2)Balance Setpoint Limits:
If the outdoor temperature is above the “Upper Balance Setpoint” (45°F by default), the heat pump is used exclusively.
If the outdoor temperature falls below the “Upper Balance Setpoint” but is above the “Lower Balance Setpoint” (35°F by default) and if the heat pump is unable to heat at a rate of 5 degrees per hour or better, the heat pump will turn off and auxiliary heat will be used until the call for heat has been satisfied.
If the outdoor temperature falls below the “Lower Balance Setpoint”, the heat pump will turn off and the auxiliary heat will be used until the call for heat has been satisfied.
The Balance Setpoint Limits can be adjusted according to the manufacturer’s specifications under “Balance Setpoint” – See Installation Settings.
3)When the
9