Inspection:
You risk electric shock if you operate this generator with a faultyGFCI
(ground fault circuit interrupter).
Test GFCI before use.
If the GFCI fails testing, do not use your generator. Contact your
Honda dealer.
CIRCUITBREAKER
GFCIRESET BUTTON GFCITEST BUTTON
OFF
Always check GFCI operation before using the generator.
Unplug all tools and appliances from the generator.
Start the engine.
Turn the circuit breakerto the ON position.
Turn the Auto Throttle switch to the OFF position.
Press the GFCI TEST button. The RESET button should extend, and
the circuit breaker should switch to the OFF position.
If the GFCI and circuit breaker do not function as described, take the
generator to an authorized Honda generator dealer for repair.