Honeywell GM-1 Operation, ADisplay Panel, BReset and Silence Switches, CDIP Switch Setting

Models: 19546GM1 GM-1

1 13
Download 13 pages 41.4 Kb
Page 10
Image 10
3 Operation

3 Operation

ADisplay Panel

A 20-segment Bargraph Display indicates the gas concentration level. The bottom LED is always lit to indicate power to the display.

The Warning LED indicates the warning level as determined by the warning setpoint has been exceeded. The Warning LED and Warning Relay operate together and never latch.

The Alarm LED indicates the alarm level as determined by the alarm setpoint has been exceeded. The Alarm LED and Alarm Relay are independently latchable or non-latchable as determined by the DIP switch on the main board. Standard factory settings are to latch the LED and not latch the relay.

The Power LED indicates power to the monitoring unit. This LED will flash during the one minute power up delay indicating that all relays are held in the normal condition to allow for sensor stabilization during power up.

The Fault LED indicates a signal input of less than

1.4mA (0.14 volts) at TP Sig. The Fault LED and Fault Relay always latch.

BReset and Silence Switches

Pushing the Reset switch will reset the fault light, fault relay, alarm light, and alarm relay. If either condition still exists, the appropriate light and relay will return to its tripped state after a time delay.

Pushing the Silence switch will silence the horn on the bottom of the Manning GM-1 until the next event occurs. The horn is triggered by a fault or an alarm condition. The horn will clear itself if the alarm and fault relay clear. A warning condition does not trigger the horn.

CDIP Switch Setting

The two position DIP switch in the center of the bottom board controls the latching of the alarm light and alarm relay. Switch 1 (left) controls the alarm relay. Switch 2 (right) controls the alarm light. Putting the switch in the on (up) position will latch the corresponding function. Putting the switch in the off (down) position will cause the corresponding function to be not latched (see Figure 3).

This allows the alarm condition to remain activated if desired even if the gas concentration goes back to below the setpoint.

Figure 3: Warning adjustment and DIP switch settings

TP

WARNING

ALARM

 

1 2

SW1

 

TP

ADJUST

 

 

 

ADJUST

 

 

 

 

GND

+20V

 

 

 

BOT TOP

 

7

TP

TP

TP

AA

 

 

 

WARNING

ALARM

SIG

 

 

 

WARNING

 

ALARM

 

FAULT

DRAW

 

RELAY

 

RELAY

 

RELAY

 

 

 

 

 

 

CURRENT

 

 

 

 

 

 

TP

1

6

 

 

 

 

 

 

 

+ C11

 

+

 

+

FUSE RATING 250V 1.0 AMP

SHLD GND

+24

SIG

L

N

NO

C

NC

NO

C

NC

NO

C

NC

 

120 VAC

 

WARNING

 

 

ALARM

 

 

FAULT

 

 

 

 

RELAY*

 

 

RELAY*

 

 

RELAY*

 

MODEL G/M

MAINBOARD REV D

 

 

 

 

 

Warning adjust pot

 

0.4 - 2.0 V

 

 

 

 

 

 

 

 

 

 

VDC

 

 

DIP switches on

 

 

 

 

 

 

 

 

 

 

bottom of board

 

 

 

 

 

Do Not Adjust!

 

 

 

 

 

Black

Red

Factory set pots

-

 

+

 

 

 

 

 

 

 

 

Risk of electrical shock.

Potential hazard.

Manning GM-1 Gas Monitoring Alarm System 19546 GM1 07/09 REVD Copyright © 2009 Honeywell Analytics. All Rights Reserved.

10

Page 10
Image 10
Honeywell GM-1, 19546GM1 installation manual Operation, ADisplay Panel, BReset and Silence Switches, CDIP Switch Setting