2.Set the dipswitches on the PRO22IC (S1) to: Baud Rate is 38, 400 bps
Flow Control is ON
Panel Address is 1
S1
8 | OFF (PASSWORD OFF) |
7ON (BAUD RATE)
6 ON (BAUD RATE)
5 ON (FLOW CONTROL)
4 | OFF | (PANEL ADDRESS) |
3 | OFF | (PANEL ADDRESS) |
2 | OFF | (PANEL ADDRESS) |
1 ON (PANEL ADDRESS)
3.Set the jumpers on the PRO22IC
Jumper
J14 | OFF | (NETWORK ENABLED) |
J12 | ON | (PORT 2 EOL ACTIVE) |
J13 | ON | (PORT 3 EOL ACTIVE) |
J4 | 2 AND 3 ON | |
J5 | 2 AND 3 ON | |
J6 | 2 AND 3 ON | |
J9 | ON |
|
4.Mount the PRO22EN to the PRO22IC (Mounting instructions on Page 15)
5.Finish Installation of
6.Connect the Networked Computer to the Ethernet Card using CAT5 cable.