Installation Guide | 15 |
5.Connect wiring to alarm input sensors or install jumper wire as appropriate.
6.Connect relay output wiring as appropriate.
7.Connect communications wiring to the Intelligent Controller.
8.Recheck wiring for correct connections and continuity.
9.When all boards have been installed, connect the Power Supply Cord for proper connections and power.
10.Setup the panel controls using the host software.
Specification
The Two Reader is for use in low voltage, class 2 circuits only.
Primary power: 12VDC±10% 400mA
Relay contacts:
Relays 1 & 3 outputs,
Relays 2 & 4 & 5 & 6 outputs,
Inputs:
8 supervised, End of Line resistors 1k ohm ± 1% tolerance 2 unsupervised dedicated inputs
Reader interface |
|
|
Reader power |
| 5 VDC (5 - 6.2) or 12 VDC |
Reader LED output | TTL compatible, high > 3V, low < 0.5V, 5mA | |
|
| source/sink max. |
Reader buzzer output | Open collector, 5 VDC open circuit max. 10mA sink max. | |
Reader data inputs | TTL compatible inputs | |
Communication: |
|
|
9,600 to 38,400 bps | ||
Wire requirements: |
|
|
Power | 1 twisted pair, 18AWG | |
24AWG, 4,000 feet (1,200m) max., | ||
| 23pf) (Belden 9842 or equivalent.) | |
Alarm inputs | 1 twisted pair per input, 30 ohms max. | |
Outputs | As required for the load | |
Readers | 6 conductors, 18AWG, 500 feet (150m) max. shield and drain | |
Mechanical: |
|
|
Dimension | 5.5" (140mm) W x 9" (229mm) L x 1" (25mm) H | |
Weight | 12 oz. (340g) nominal | |
Environment: |
|
|
Temperature | 0°C to +49°C, operating, | |
Humidity | 0% to 85% RHNC |