Honeywell PRO-2200 installation manual Alarm Contact Wiring, Control Output Wiring, LED Output

Models: PRO-2200

1 20
Download 20 pages 9.1 Kb
Page 13
Image 13
Single Wire Reader LED Control Configuration

PRO-2200 Two Reader Module PRO22R2Installation Guide13

Single Wire Reader LED Control Configuration

LED Output->

High

Tri-Stated

Low

Single Color LED

LED On

LED Off

LED Off

 

 

 

 

Bi-Color LED

Green LED On

Both LEDs Off

Red LED On

 

 

 

 

To fully utilize each reader port, a 6-conductor cable (18AWG) is required. Reader port configuration is set via host software.

Alarm Contact Wiring

Inputs 1 to 8 may be configured to use normally open or normally closed contacts and non-supervised or supervised (with standard ±1 tolerance 1K ohm). Four of these inputs have default functional definitions, but all eight can be configured to monitor general- purpose alarm sensors.

NO

NC

1K 1K

1K 1K

1

2

3

4

By default, Input 1 is defined as the Door Status Input corresponding to reader 1 and Input 2 is defined as the REX input corresponding to reader 1. Also by default, Input 3 is defined as the Door Status Input corresponding to reader 2 and Input 4 is defined as the REX input corresponding to reader 2.

Inputs 5, 6, 7, and 8 are general purpose inputs that can be used to monitor alarm sen- sors or can be used as control inputs. Inputs 7 and 8 are not accessible when the board is rack mounted.

Inputs TMP and PFL are typically used for monitoring cabinet tamper and power failure respectively. These 2 inputs are not supervised and are not accessible when the board is rack mounted. These inputs were primarily provided for the case when this board is mounted remotely and can not take advantage of the tamper and power fail detect inputs on the controller board. If these inputs are not used, install a short piece of wire at the input to indicated safe condition.

Input configuration including debounce and hold time is set via host software.

Control Output Wiring

Six form-C relay contacts are provided for controlling door strike or other devices. Each may be assigned to door-related functions or general-purpose output. They are configurable as standard (energize to activate) or fail-safe (de-energize to activate) via host software.

The energized or ON time of each relay can be configured using Pulse control for single or repeating pulses via host software. The energized or ON time for a single pulse can be extended up to 24 hours. For repeating pulses, the on/off time can be defined in 0.1 second increments and be repeated up to 255 times.