Single Wire Reader LED Control Configuration
LED | High | Low | |
Single Color LED | LED On | LED Off | LED Off |
|
|
|
|
Green LED On | Both LEDs Off | Red LED On | |
|
|
|
|
To fully utilize each reader port, a
Alarm Contact Wiring
Inputs 1 to 8 may be configured to use normally open or normally closed contacts and
NO
NC
1K 1K
1K 1K
1
2
3
4
By default, Input 1 is defined as the Door Status Input corresponding to reader 1 and Input 2 is defined as the REX input corresponding to reader 1. Also by default, Input 3 is defined as the Door Status Input corresponding to reader 2 and Input 4 is defined as the REX input corresponding to reader 2.
Inputs 5, 6, 7, and 8 are general purpose inputs that can be used to monitor alarm sen- sors or can be used as control inputs. Inputs 7 and 8 are not accessible when the board is rack mounted.
Inputs TMP and PFL are typically used for monitoring cabinet tamper and power failure respectively. These 2 inputs are not supervised and are not accessible when the board is rack mounted. These inputs were primarily provided for the case when this board is mounted remotely and can not take advantage of the tamper and power fail detect inputs on the controller board. If these inputs are not used, install a short piece of wire at the input to indicated safe condition.
Input configuration including debounce and hold time is set via host software.
Control Output Wiring
Six
The energized or ON time of each relay can be configured using Pulse control for single or repeating pulses via host software. The energized or ON time for a single pulse can be extended up to 24 hours. For repeating pulses, the on/off time can be defined in 0.1 second increments and be repeated up to 255 times.