A.8 | Typical Smart Meter Indications, Continued | |||||||
Operation error codes |
|
|
| |||||
Table | ||||||||
Table | ||||||||
|
|
|
|
|
|
| ||
| If error indication is . . . | Then, it means |
| |||||
|
|
|
|
|
|
| You have tried to set local Zero or Span adjustment in a | |
| VAR |
|
|
|
| UPPER | Series 100 transmitter that does not support this option. | |
|
|
|
|
| ||||
|
|
|
|
|
|
| ||
| SEL. |
|
|
|
| VALUE |
|
|
|
|
| % | 100 |
|
|
| |
| 0 |
|
|
| ||||
| E r 0 |
|
| UNITS |
|
| ||
|
|
|
| % | S E T |
|
| |
|
|
|
|
|
|
|
| |
|
|
| ANALOG |
|
| LOWER |
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
| VALUE |
|
|
|
|
|
|
|
| You have tried to set a pressure type engineering unit for a |
|
|
|
|
|
| transmitter in SQUARE ROOT mode (FLOW) or have tried |
|
|
|
|
|
| |
SEL. |
|
|
| VALUE | to set a flow type engineering unit for a transmitter in | |
VAR |
| % | 100 | UPPER | LINEAR mode (pressure). After this error is displayed, the | |
|
|
| ||||
0 | UNITS | |||||
E r 1 |
|
| meter will return to the unit # (EU#) of the Engineering Unit | |||
% | S E T | |||||
|
|
|
|
| ||
|
| ANALOG |
|
| LOWER | it was displaying before the set function was invoked. You |
|
|
|
|
| may then select another unit or exit in the normal fashion. | |
|
|
|
|
| VALUE | |
|
|
|
|
|
|
|
|
|
|
|
|
| You have tried to select a process variable for the |
|
|
|
|
|
| transmitter using the VAR SEL. button. The Variable Select |
|
|
|
|
|
| |
SEL. |
|
|
| VALUE | button is | |
VAR |
| % | 100 | UPPER |
| |
|
|
|
| |||
0 | UNITS |
| ||||
E r 2 |
|
|
| |||
% | S E T |
| ||||
|
|
|
| |||
|
|
|
|
|
| |
|
| ANALOG |
|
| LOWER |
|
|
|
|
|
|
| |
|
|
|
|
| VALUE |
|
|
|
|
|
|
| You have tried to set Lower or Upper display limit for | |
|
|
|
|
|
| pressure type engineering units (EU1 to EUC), or Lower | |
|
|
|
|
|
| ||
SEL. |
|
|
| VALUE | display limit for flow type engineering units (EUD,EUE) or | ||
VAR |
| % | 100 | UPPER | CUSTOM unit (EUF) in transmitter configured for SQUARE | ||
|
|
| |||||
0 |
| ||||||
E r 3 |
|
| UNITS | ROOT output. Or, you have tried to set upper display limit | |||
% | S E T | for flow or Custom unit in transmitter with SQUARE ROOT | |||||
|
| ANALOG |
|
| VALUE | output and URV set to zero (0). In SQUARE ROOT mode, | |
|
|
|
|
| LOWER |
|
|
|
|
|
|
|
| the transmitter’s URV cannot equal zero. The Lower and | |
|
|
|
|
|
| Upper display limits only apply for CUSTOM (EUF) unit in | |
|
|
|
|
|
| transmitter configured for LINEAR output. The Upper | |
|
|
|
|
|
| display limit also applies for FLOW (EUD,EUE) and | |
|
|
|
|
|
| CUSTOM (EUF) units with transmitter in SQUARE ROOT | |
|
|
|
|
|
| mode , but the Lower display limit is fixed at zero (0) and | |
|
|
|
|
|
| cannot be changed. | |
|
|
|
|
|
|
|
|
|
|
|
|
|
| Continued on next page | |
2/05 | ST 3000 Release 300 Installation Guide | 81 |