T8775A,C THE DIGITAL ROUND™
Rc | B | |
G | ||
2 | ||
Y | ||
R | ||
W | ||
|
COMPRESSOR |
CONTACTOR |
| HEATING | FAN |
1 | RELAY OR | RELAY |
| VALVE COIL |
|
1 |
FUEL SWITCH | M19497 |
Fig. 12. Fuel switch.
1POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2REMOVE FACTORY INSTALLED JUMPER BETWEEN R AND RC.
M19517
Fig. 10. Typical hookup of T8775C in heat-cool system
with two transformers.
4
| O | |
| B | |
| Rc | |
2 | G | |
Y 3 | ||
R | ||
| W |
DIP Switch
To adjust the heat cycle rate or the Fahrenheit/Celsius temperature display, locate DIP switch 1, 2 and 3 on the back of the thermostat. See Fig. 13.
BACK OF THERMOSTAT
| COMPRESSOR |
| HEAT |
| CHANGEOVER | ||
| CONTACTOR | ||
|
| VALVE | |
|
|
| |
1 | FAN |
| COOL |
|
| ||
| RELAY | CHANGEOVER | |
| VALVE | ||
|
|
| |
1 | POWER SUPPLY. PROVIDE DISCONNECT MEANS | ||
| AND OVERLOAD PROTECTION AS REQUIRED. | ||
2 | FACTORY INSTALLED JUMPER. | ||
3 | USE A JUMPER WIRE (NOT SUPPLIED) TO CONNECT W TO Y. | ||
4 | USE EITHER O OR B FOR HEAT PUMP CHANGEOVER. | ||
|
|
| M19516 |
Fig. 11. Typical hookup of T8775C in single-stage heat
pump system.
CUSTOMIZE THERMOSTAT
Setting Fuel Switch (T8775C only)
The fuel switch is preset at the factory in the F position. See Fig. 12. This is the correct setting for gas or oil systems. If the T8775C is being installed on an electric heat system, or a heat pump, set the switch to the E position. The E position allows the fan to turn on immediately with the heating equipment in a system where the G terminal is connected.
| 3 |
| 2 |
ON | 1 |
M19567
DIP SWITCH
Fig. 13. DIP switch.
Set Heat Cycle Rate
Use DIP switches 1 and 2 to set the heat cycle rate. See Table 1.
Table 1. Heat Cycle Rate.
|
|
|
|
| Cycles | DIP | DIP |
Heating System | Per | Switch | Switch |
Hour | 1 | 2 | |
Steam, Gravity | 1 | On | On |
|
|
|
|
High Efficiency Warm Air (90%+ | 3 | Off | On |
efficiency), Hot Water, Heat Pump |
|
|
|
Gas or Oil Warm Air (factory setting) | 6 | Off | Off |
|
|
|
|
Electric Warm Air | 9 | On | Off |
|
|
|
|
In Floor Radiant Heat | Check with manufacturer | ||
| for recommended cycle | ||
| rate. |
|
|
5 |