PRO TH2000DH/TH1000DH Series
769-2609EFS—03
ENGLISH

Setup function Settings & options (factor y default in bold)

5 Heating cycle rate
(CPH:cycles/hour)
TH2110DH, TH1110DH
and TH1100DH
5 For gas or oil furnaces of less than 90% efficiency
1 Forsteamorgravitysystems
3 Forhotwatersystems&furnacesofover90%efficiency
6 Forelectricfurnaces
[Othercyclerateoptions:2or4CPH]
6 Auxiliary heat
cycle rate (CPH)
TH2210DH and
TH1210DH
5 For gas or oil furnaces of less than 90% efficiency
1 Forsteamorgravitysystems
3 Forhotwatersystems&furnacesofover90%efficiency
6 Forelectricfurnaces
[Othercyclerateoptions:2or4CPH]
9 Compressor
cycle rate (CPH) 3 Recommended for most compressors
[Othercyclerateoptions:1,2,4,5,or6CPH]
13 Early Start (TH2110DH
and TH2210DH) 1 On **See page 8
0 Off
14 Temperature
display 0 Fahrenheit
1 Celsius
15 Compressor
protection 5 Five-minute compressor off time (See page 8)
0 Nocompressorofftime
20 Clock display
(TH2110DH and
TH2210DH)
0 12-hour display
1 24-hourdisplay
25 Lower temperature
range (TH1100DH only) 0 Standard range 40°F to 90°F (4.5°C to 32°C)
1 Lowerrange(forgaragemode)35°Fto90°F
(1.5°Cto32°C)
40 Restore program
schedule to default
(TH2110DH and
TH2210DH)
0 Off
1 On-programscheduledefaultsettingsarelistedinthe
operatingmanual
Installer setup
CAUTION: EQUIPMENT DAMAGE HAZARD
Compressorprotectionisbypassedduringtesting.Topreventequipmentdamage,
avoidcyclingthecompressorquickly.