Honeywell V8043A Mounting, Wiring, Sweat Copper Models, Align the parallel flat surfaces in

Models: V8043E V8043A V8043 V8043F

1 5
Download 5 pages 14.43 Kb
Page 2
Image 2
MOUNTING
Parallel flat surfaces align with Notch on side of valve body

MOUNTING

The valve can be mounted in any position on a vertical line. See Fig. 2. If the valve is mounted horizontally; the actuator must be even with or above the center line of the piping. Make sure to leave enough room above the actuator to remove the cover for servicing.

Mount the valve directly in the tube or pipe after the coil. Make sure that the flow through the valve is in the direction indicated by the arrow stamped on the valve body.

thermostat or controller connected to the valve so that the valve runs through its cycle. Make sure the valve runs smoothly and positively from closed to open to closed again. (See Operation and Checkout Sections.)

TO REMOVE THE ACTUATOR FROM THE VALVE BODY (See Fig. 3)

NOTE!

It is not necessary to drain the hydronic system if the valve body assembly remains in the pipe line.

1. Switch power supply OFF. Disconnect

electrical leads carefully, noting the

position and colour of each lead.

2. Place the manual lever in the MAN.

OPEN position.

4.Line up motor coupling to the parallel flat surfaces in double-D shaft of body and fit the actuator onto the valve body, ensuring that the shaft seats correctly. (See Fig. 5)

5.Snap actuator onto body by pressing down.

6.The manual lever may be released manually, but it is also automatically released when the valve is operated electrically.

Double-D

Shaft

Notch

 

 

THERMOSTAT

TO

 

(TYPICALLY T87F)

LINE

 

 

 

 

TO CIRCULATOR

 

YELLOW

OR ANOTHER VALVE

 

 

 

LEADS

 

 

 

RED LEADS

 

MOTOR

 

 

 

AUXILIARY

 

 

SWITCH

M5953

Fig. 6 - Typical wiring for V8043E, V8044E.

HORIZONTIAL

PIPING

VERTICAL

PIPING

M10162

3. Remove actuator by fully depressing

spring release button and lift it straight

off of the body.

Fig. 4 - Shaft Position

Actuator

Coupling

R

THERMOSTAT (TYPICALLY T87F)

END SWITCH

TO CIRCULATOR OR ANOTHER VALVE

Fig. 2 - Mounting Positions

Sweat Copper Models

1.

Use new, properly reamed pipe, free

 

from dents or corrosion.

2.

Place the valve on the pipe. Set the

 

manual opening lever to MAN. OPEN

 

position before applying heat. This

 

1. PLACE MANUAL

AUTO

LEVER IN OPEN

OPEN

 

POSITION

2. DEPRESS

 

LOCKING

 

BUTTON

3. LIFT ACTUATOR

 

STRAIGHT UP

Notch Tab

Notch

TH TR TH TR

1

L1

(HOT)

L2

24V TRANSFORMER

protects the plug inside the valve by

removing it from the seat.

3. Sweat the joints, keeping the outer

surface free from solder. DO NOT use

silver solder because of the high

melting temperature required.

TO INSTALL A COMPLETE VALVE (V8043):

1.Disconnect power supply before connecting wiring to prevent electrical shock or equipment damage.

2.Install valve into pipe on the return side of the coil. (See Mounting Section.)

3.Make wiring connections to valve. (Refer to Wiring section for proper instructions.)

4.Inspect the valve installation to ensure that all connections and adjustments have been correctly made. Adjust the

Fig. 3 - Removing Actuator from Valve Body

TO INSTALL REPLACEMENT ACTUATOR ON THE VALVE BODY

1.Align the parallel flat surfaces in

double-D shaft of valve body with notch in side of body (i.e. 90° to water flow.) See Fig. 4. This makes actuator attachment easier.

2.Wiring connections may be made either before or after actuator installed on valve body.

3.Place the manual lever on the actuator in the MAN. OPEN position.

Fig. 5 - Installing Actuator

WIRING

Disconnect the power supply before connecting wiring to prevent electrical shock or equipment damage.

All wiring must comply with local codes and ordinances. Connections to the individual valves are shown in Fig. 6 and 7. See Fig. 8 through 14 for typical hookups.

If replacing a Taco, Dole, Flair or White Rodgers 3-wire valve with a 2-wire V8043E or F, see Fig. 15 through 27. Check that the pressure rating of the new valve is appropriate for the application.

1POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

M5952

Fig. 7 - Typical wiring for V8043F.

T822

 

T822

 

T822

 

 

 

 

 

L1

(HOT)

L2

1

2

2

2

V8043A

V8043A

V8043A

1POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

2 CONNECT V8043A BLACK LEADWIRE TO THERMOSTAT.

M10168

Fig. 8 - T822 Thermostat, V8043A valve hookup.

3

4

Page 2
Image 2
Honeywell V8043A Mounting, Wiring, Sweat Copper Models, Align the parallel flat surfaces in, To Install A Complete Valve