2. Water-Cooled Condenser

a) Connection to an Open Drain System

Condenser water supply inlet is 1/2" female pipe thread (FPT). A minimum of 3/8" OD copper tubing is recommended for the condenser water supply line.

A condenser water supply line shut-off valve and drain valve should be installed.

Condenser drain outlet is 3/8" FPT. A minimum of 3/8" OD hard pipe is recommended for the condenser drain line.

In some areas, a back flow preventer may be required in the cooling water circuit.

Icemaker Water

Supply Inlet

1/2" FPT

Condenser Water

Supply Inlet

1/2" FPT

Icemaker

Icemaker Water Supply Line Shut-Off Valve

Condenser

Drain Outlet

3/8" FPT

Condensation

Drain Outlet

3/8" OD Stainless

Tube

Icemaker

Drain Outlet

3/4" FPT

Bin

Bin Drain Outlet 3/4" FPT

Condenser Water Supply Line Shut-Off Valve

Icemaker Water Supply Line

Drain Valve

Condenser Water Supply Line Drain Valve

Separate piping to approved drain. Leave a two-inch (5 cm) vertical air gap between the end of each pipe and the drain.

Two-inch (5 cm) air gap

Floor Drain

Fig. 12

KM-650MWH

 

Connection to an Open Drain System