Hoshizaki KML-700MWH-M Connection to an Open Drain System, Water-CooledCondenser, Fig

Models: KML-700MWH-M

1 20
Download 20 pages 54.96 Kb
Page 11
Image 11
2. Water-Cooled Condenser

2. Water-Cooled Condenser

a) Connection to an Open Drain System

Condenser water supply inlet is 1/2" female pipe thread (FPT). A minimum of 3/8" OD copper tubing is recommended for the condenser water supply line.

A condenser water supply line shut-off valve and drain valve should be installed.

Condenser drain outlet is 3/8" FPT. A minimum of 3/8" OD hard pipe is recommended for the condenser drain line.

In some areas, a back flow preventer may be required in the cooling water circuit.

Icemaker

 

Water Supply

Icemaker

Inlet

 

1/2" FPT

 

Condenser

 

Drain Outlet

 

3/8" FPT

 

Condenser Water

 

Supply Inlet

 

1/2" FPT

 

Icemaker

Bin

 

Drain Outlet

 

3/4" FPT

 

Icemaker Water Supply Line

Shut-Off Valve

Condenser Water Supply Line

Shut-Off Valve

Icemaker Water Supply Line

Drain Valve

Condenser Water Supply Line

Drain Valve

Bin Drain Outlet 3/4" FPT

Separate piping to approved drain. Leave a 2-inch (5-cm) vertical air gap between the end of each pipe and the drain.

2-inch (5-cm) air gap

Floor Drain

Fig. 4

KML-700MWH-M

 

Connection to an Open Drain System

11

Page 11
Image 11
Hoshizaki KML-700MWH-M instruction manual Water-CooledCondenser, a Connection to an Open Drain System, Fig