QuickSpecs
HP Basic Power Distribution Units
Basic PDU Family Information
Hardwired PDU  | H5M75A  | 46A  | 11040VA @230V  | 
  | Terminal block  | 
  | 3 x 20A  | 30 x IEC C13  | |
  | 
  | 
  | 
  | 
  | for hardwired  | 
  | 
  | 6 x IEC C19  | |
  | 
  | 
  | 
  | 
  | 
  | installation  | 
  | 
  | 
  | 
5.7kVA Dual  | H5M63A  | 27.7A  | 5764VA @208 3Ø  | 8ft(2.4m) cord  | 
  | 3 x 20A  | 20 x IEC C13  | ||
Voltage PDU  | 
  | 20A  | 
  | 
  | 
  | with attached  | 
  | 
  | 3 x NEMA 5-  | 
  | 
  | 3 phase WYE  | 
  | 
  | 
  | NEMA   | 
  | 
  | 20R  | 
8.6kVA Dual  | H5M64A  | 41.5A  | 8646VA @208 3Ø  | 8ft(2.4m) cord  | 
  | 3 x 20A  | 20 x IEC C13  | ||
Voltage PDU  | 
  | 30A  | 
  | 
  | 
  | with attached  | 
  | 
  | 3 x IEC C19  | 
  | 
  | 3 phase WYE  | 
  | 
  | 
  | NEMA   | 
  | 
  | 3 x NEMA 5-  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 20R  | 
8.6kVA PDU  | H5M62A  | 41.5A  | 8646VA @208 3Ø  | 8ft(2.4m) cord  | 
  | 3 x 20A  | 24 x IEC C13  | ||
  | 
  | 30A  | 
  | 
  | 
  | with attached  | 
  | 
  | 6 x IEC C19  | 
  | 
  | 3 phase Delta  | 
  | 
  | 
  | NEMA   | 
  | 
  | 
  | 
11kVA PDU  | H5M72A  | 16A per phase  | 11084VA  | 
  | 8ft(2.4m) cord  | 
  | 3 x 16A  | 24 x IEC C13  | |
  | 
  | 16A  | 
  | @ 400V 3Ø  | 
  | with attached  | 
  | 
  | 6 x IEC C19  | 
  | 
  | 3 phase WYE  | 
  | 
  | 
  | IEC 516P6  | 
  | 
  | 
  | 
Full Height vertical models | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | |
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | ||
11kVA PDU  | H5M73A  | 16A per phase  | 11040VA  | 8ft(2.4m) cord  | 3 x 16A  | 36 x IEC C13  | |||
  | 
  | 16A  | 
  | @ 400V 3Ø  | with attached  | 
  | 
  | 6 x IEC C19  | |
  | 
  | 3 phase WYE  | 
  | 
  | IEC 516P6  | 
  | 
  | 
  | |
11kVA PDU  | H5M67A  | 24A per phase  | 11040VA  | 8ft(2.4m) cord  | 3 x 20A  | 36 x IEC C13  | |||
  | 
  | 30A  | 
  | @400V 3Ø  | with attached  | 
  | 
  | 6 x IEC C19  | |
  | 
  | 3 phase WYE  | 
  | 
  | IEC 530P6  | 
  | 
  | 
  | |
480/277 Volt models | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | |
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | ||
13.2kVA PDU  | H3X07A  | 480V 30A 3  | 16A per phase  | 13301VA  | 9.8ft(3M) cord  | 3 x 20A  | 15 x   | ||
  | 
  | phase WYE  | 
  | @480V 3Ø  | with attached  | 
  | 
  | 
  | |
  | 
  | 
  | 
  | 
  | IEC 530P7  | 
  | 
  | 
  | |
19.9kVA PDU  | H3X08A  | 480V 30A 3  | 24A per phase  | 19952VA  | 9.8ft(3M) cord  | 6 x 20A  | 30 x   | ||
  | 
  | phase WYE  | 
  | @480V 3Ø  | with attached  | 
  | 
  | 
  | |
  | 
  | 
  | 
  | 
  | IEC 530P7  | 
  | 
  | 
  | |
*NOTE: HP Basic PDU models H5M56A and H5M57A require an IEC 
NOTE: Please refer to the Power Cord Matrix for more information on power cords/cable part numbers, input/output descriptions. http://www.hp.com/go/powercordmatrix.
Disclaimer: HP makes no recommendations regarding power connector manufactures. Please consult a licensed professional to determine the best connector or receptacle for your specific needs.
DA - 14557 North America — Version 7 — October 1, 2013  | Page 10  |