HP Performance Optimized Data Center (POD) 240a manual HP POD 240a security

Models: Performance Optimized Data Center (POD) 240a

1 26
Download 26 pages 60.09 Kb
Page 24
Image 24

HP POD 240a security

The HP POD 240a is equipped with standard key lock hardware at each personnel entry door and six external electrical cabinets. Each personnel entry door includes a door access contact that can be connected to the customer facility security system. Conduit and junction boxes are provided for customer installed controlled access systems.

Additional options for controlled access security includes:

Electronic card reader

12-digit security code keypad

Magnetic lock on each entry door

Fire, safety, and security notifications

Dry contacts are provided to enable the connection between the HP POD 240a fire alarm system and the customer facility fire system. If the HP POD 240a is connected to the customer facility systems, then the HP POD 240a-initiated alarms, notify the facility systems.

The customer must provide an independent connection for each system listed in the following table.

Alarm

Meaning

 

 

Fire prevention alarm

Smoke has been detected in the HP POD 240a.

Fire suppression

The suppression system alarm has been activated, and

system (optional)

gas will be dispersed to suppress a fire.

Security

A security breach has occurred.

EPO

The EPO system has been activated by an EPO button

 

or thermal event, and shut down the HP POD 240a.

 

 

The electrical layout of the fire alarm system is as described in the schematic drawing that is supplied with the HP Performance Optimized Datacenter (POD) 240a Operations and Maintenance Manual.

Supported facility connections 24

Page 24
Image 24
HP Performance Optimized Data Center (POD) 240a manual HP POD 240a security, Fire, safety, and security notifications