HP POD 240a security
The HP POD 240a is equipped with standard key lock hardware at each personnel entry door and six external electrical cabinets. Each personnel entry door includes a door access contact that can be connected to the customer facility security system. Conduit and junction boxes are provided for customer installed controlled access systems.
Additional options for controlled access security includes:
Electronic card reader
Magnetic lock on each entry door
Fire, safety, and security notifications
Dry contacts are provided to enable the connection between the HP POD 240a fire alarm system and the customer facility fire system. If the HP POD 240a is connected to the customer facility systems, then the HP POD
The customer must provide an independent connection for each system listed in the following table.
Alarm | Meaning |
|
|
Fire prevention alarm | Smoke has been detected in the HP POD 240a. |
Fire suppression | The suppression system alarm has been activated, and |
system (optional) | gas will be dispersed to suppress a fire. |
Security | A security breach has occurred. |
EPO | The EPO system has been activated by an EPO button |
| or thermal event, and shut down the HP POD 240a. |
|
|
The electrical layout of the fire alarm system is as described in the schematic drawing that is supplied with the HP Performance Optimized Datacenter (POD) 240a Operations and Maintenance Manual.