Hubbell Electric Heater Company HE, HSE Section Iv - Troubleshooting, Symptom, Probable Cause

Models: HSE HE

1 22
Download 22 pages 19.05 Kb
Page 13
Image 13

SECTION IV – TROUBLESHOOTING

Symptom

Probable Cause

Corrective Action / Remedy

No hot water

Circuit breaker tripped at source.

Reset circuit breaker.

 

High limit switch tripped.

Reset high limit switch.

 

 

 

 

Loose wires.

Tighten wires. Torque screws per torque

 

 

chart included in Section VI.

 

Heating element inoperable.

Check heating element operation by

 

 

clamping an Amprobe around each wire

 

 

to the element. The ampere reading

 

 

should agree with the nameplate ‘AMP’

 

 

figure.

 

Low line voltage.

Have source electrical system checked

 

 

by an electrician.

 

Faulty thermostat.

Move thermostat dial through full range.

 

 

A definite ‘click’ should be heard. If not,

 

 

replace thermostat.

 

Magnetic contactor does not

Replace complete magnetic contactor.

 

energize.

Because of the design of this particular

 

 

contactor, it is more desirable to replace

 

 

complete control rather than rebuilding

 

 

coil, contacts and springs, etc.

Water temperature

Faulty thermostat.

Check thermostat adjustment. Monitor

below settings at all

 

thermostat as described in Section III,

times

 

Quarterly Inspection. Replace if

 

 

necessary.

 

Heating element not working on

Check to see that heating element is

 

all phases

working on all phases, by checking the

 

 

resistance (ohms) value for each

 

 

element and comparing with the chart

 

 

included in Section VI.

 

Heater improperly sized

Verify heater is properly sized for the

 

 

flow rate and temperature rise of your

 

 

system. See formulas included in

 

 

Section VI. Replace elements with

 

 

proper size as necessary.

Relief valve discharges

Excessive temperature or

Temperature and pressure relief valves

continuously

pressure in tank

are made to operate if the water

 

 

temperature exceeds 210°F or water

 

 

pressure exceeds the pressure rating of

 

 

the safety relief valve. If trouble is

 

 

excessive temperature, then thermostat is

 

 

not shutting off at the right setting and

 

 

thermostat must be replaced.

 

 