Hubbell Electric Heater Company J manual Troubleshooting Flow Charts, Diagram

Models: J

1 31
Download 31 pages 12.76 Kb
Page 23
Image 23
TROUBLESHOOTING FLOW CHARTS

TROUBLESHOOTING FLOW CHARTS

 

 

 

 

 

 

 

 

 

 

 

Is the

 

 

 

 

 

 

 

 

See 'No Display'

 

 

 

No Hot Water

 

 

 

No

 

 

 

 

 

 

 

 

 

 

 

 

 

display on?

 

 

 

 

 

 

flowchart

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Continuous Low

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Water

 

 

 

 

 

 

 

Is there an

 

 

 

 

 

 

 

 

See Error

 

 

 

Temperature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

error

 

 

Yes

 

 

Message section

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

message?

 

 

 

 

 

 

 

 

of this manual

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Verify setpoint

 

 

 

 

 

 

 

 

 

No

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check for loose

 

 

 

 

 

 

 

 

OK?

 

 

 

 

 

 

 

 

 

 

 

wires and tighten

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

as necessary

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Verify water inlet

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

pressure and

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

temperature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Magnetic

 

 

 

 

 

 

Verifythat all wires

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

are installed and in

 

 

 

 

 

 

 

 

 

 

 

 

 

contactor pull

 

No

 

 

correct positions

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OK?

 

 

 

 

 

 

 

 

 

in?

 

 

 

 

 

 

 

 

(see wiring

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

diagrams)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Correct fault

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

condition

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Correct amps

 

 

 

 

 

 

 

 

Replace faulty

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208/240V

at contactor

coil?

No

Verify T1000 configuration settings. Replace control board, if needed

YesDiagram 1 Replace contactor

OK?

 

 

 

 

 

 

 

 

 

 

 

No

 

 

 

 

 

 

 

 

 

 

 

 

 

at elements?

 

 

 

element

 

 

 

 

 

 

 

 

 

 

Unit properly

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

sized?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No

 

 

Plug probe end into RJ45 pigtail

 

 

 

 

 

 

 

 

 

 

 

(not supplied). Check ohms

 

 

 

 

 

 

 

 

 

 

 

 

across terminals 1 and 4

 

 

 

 

Do ohms

Replace with

 

(see diagrams 1 & 2). Compare

 

 

 

 

 

match?

correctly sized unit

 

this with the ohms the thermistor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

should supply for the actual

 

 

 

 

 

 

 

 

 

 

 

 

temperature in the tank

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OK?

No

Contact factory

Yes

No

Diagram 1

Thermistor Resistance vs Temperature (error ±3%)

70°F = 1188380°F = 929990°F = 7334100°F = 5828110°F = 4664120°F = 3758130°F = 3048140°F = 2488150°F = 2043160°F = 1687170°F = 1400180°F = 1169190°F = 980

 

Replace probe

 

 

 

OK?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Diagram 2

 

 

 

 

 

 

 

 

 

To verify that

 

Blue

 

 

 

 

 

 

 

 

 

1

there is water

 

 

 

 

 

 

 

 

 

 

Yellow

 

 

 

 

 

 

 

 

 

2

in the tank

 

 

 

 

 

 

 

 

 

 

Green

 

Probe End

 

 

 

RJ45 Pigtail

 

3

check for

 

Red

 

 

 

 

 

4

continuity

 

Black

 

 

 

 

 

 

 

 

 

5

between

 

 

 

 

 

 

 

 

 

 

 

White

 

 

 

 

 

 

 

 

 

6

yellow(#2) and

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ground.

 

 

 

 

 

 

 

 

 

 

 

 

23

Page 23
Image 23
Hubbell Electric Heater Company J Troubleshooting Flow Charts, Diagram, Thermistor Resistance vs Temperature error ±3%