P/N 374511B
Page 16
CONFIG MENU (continued)
PROTOCOL™ | Hand Held Device |
|
MixMatch compressor cycling is used when compressors of varying horsepowers have been installed. This algorithm allows the compressor horse power to be more closely matched with the evaporator load
There are 16 available steps for MixMatch cycling. The additional steps are accessible by
pressing the |
| arrow to view additional screens. |
|
Each step can be programmed by entering anum- ber between 1 and 63 of the step number. The Hand Held Device will use this number to display the compressors selected with an ‘X’and those not selected with a ‘0.’
The number entered and used by the Hand Held Device is a binary number. The following example describes the relationship of the number to com- pressors. Causion: If you have concerns over this programming, consult Bridgeton Refrigeration Engineering.
|
| MIXMATCH SETUP |
|
| |||
|
|
|
| COMPRSSORS | |||
SETUP |
|
| 1 | 2 | 3 | 4 | |
1 | – | 01 | – | X | 0 | 0 | 0 |
2 | – | 02 | – | 0 | X | 0 | 0 |
3 | – | 03 | – | 0 | 0 | X | 0 |
4 | – | 04 | – | 0 | 0 | 0 | X |
|
|
|
|
|
|
|
|
HUSSMANN CORPORATION • BRIDGETON, MO | 970307 |