6- AUX SENSORS
Press 6 on the Keypad to enter the Auxiliary Sensors Submenu.
AUXILIARY SENSORS provide six temperature
Analog for thermistors
Digital for thermostats.
ANALOG SETTING
ANALOG accommodates temperature readings between – 40 and + 120˚F. Set on ANALOG, an unused input will produce a – 40.
DIGITAL SETTING
When set on DIGITAL the read out will be either OPEN (not in use) or CLOSED.
Use the key to toggle between ANALOG and
DIGITAL.
Using the ENT key, move down the selections.
Press CLR. Key in your selection and press ENT. The cursor will move down to the next sensor.
Press ESC to return to AUXILIARY SENSORS MENU.
Press ESC again to return to SENSOR SETUP MENU.
Press ESC again to return to CONFIG MENU.
Hand Held Device
SENSOR SETUP MENU
AUXILIARY SENSORS
MORE ON NEXT PAGE
AUXILIARY SENSORS
AUX | SENSOR #1 |
| |
MODE | – | DIGITAL | |
NAME – |
|
|
|
TERM. SP | – | CLOSED | |
HI ALARM | – | 0 | F |
LO ALARM | – | F | |
ALARM | – | ENABLED | |
|
|
|
|
Note: Aux Sensors 7 through 12 are available only on Expansion Module.