HI ALARM

Hand Held Device

PROTOCOL

 

CONFIG MENU (continued)

3- TEMP #1

3-TEMP #1 allows you to establish set point and alarm levels for the first temperature input.

Press 3 on the Keypad to enter the TEMP #1 Submenu.

The ALM DELAY is a programmable time delay. This sets the time it will take before the control log’s the alarm.

P/N 374511B

Page 13

SENSOR SETUP MENU

1-PRESSURE #1

2-PRESSURE #2

3-TEMP #1

4-TEMP #2

5-TEMP #3

The CIRCUIT - X allows you to attach a defrost circuit to the temperature input (or vice versa).

When the circuit is in defrost, thewill be ignored.

Press CLR. Key in your selection and press ENT.

Using the key, toggle ENABLED or DISABLED. Press ENT.

Press ESC to return to SENSOR SETUP MENU.

4- TEMP #2

Press 4 on the Keypad to enter the TEMP #2 Submenu. Follow instructions above.

5- TEMP #3

Press 5 on the Keypad to enter the TEMP #3 Submenu.

If split suction is installed, TEMP #3 may be factory set to read head pressure instead of temperature. This is accomplished by changing the input mode to Pressure.

If split suction is not installed, TEMP #3 is a designated temperature input; but if you prefer it can be factory set as a pressure input.

Using the key, toggle TEMP or PRESS. Press

ENT.

Press ESC to return to SENSOR SETUP MENU.

 

TEMPERATURE # 1

 

SET PT

-

XX F

3

HI ALARM

-

XX F

LO ALARM

-

XX F

 

ALARM

-

ENABLE

 

ALM DELAY

-

30 MIN

 

CIRCUIT

-

X

 

 

 

 

 

TEMPERATURE # 2

 

SET PT

-

XX F

4

HI ALARM

-

XX F

LO ALARM

-

XX F

 

ALARM

-

ENABLE

 

ALM DELAY

-

30 MIN

 

CIRCUIT

-

X

 

 

 

 

 

TEMPERATURE # 3

 

INPUT MODE

-

TEMP

5

SET PT

-

XX F

HI ALARM

-

XX F

 

 

 

 

LO ALARM

-

XX F

 

ALARM

-

ENABLE

 

ALM DELAY

-

30 MIN

 

CIRCUIT

-

X

 

 

 

 

Note: When using T3 for a pressure reading, remember to place the hardware switch on the main control board in the pressure position.

970307

HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 (Printed in U.S.A.)