Hand Held Device

PROTOCOL

 

CONFIG MENU (continued)

 

2- SENSOR SETUP

Press 2 on the Keypad to enter the Sensor Setup Submenu. This screen has 6 menus.

1- PRESSURE #1

Press 1 on the Keypad to enter the Pressure #1 Submenu.

PRESSURE #1 controls the suction pressure for the Protocol Control. Press the CLR key. Key in the applicable suction pressure in psig for HI ALARM and press ENT. Repeat for LO ALARM.

Pressure Transducers are supplied in one of three ranges:

0 to 100

0 to 200

0 to 500

Using the key, toggle to the range of the transducer used. Press ENT.

Offset allows manual calibration for the pressure transducer. Manual calibration is achieved by entering a number between -5 and +5. This number will then be used to offset the pressure reading by the entered amount.

WARNING: Improper calibration of the transducer could lead to unpredictable operation of the control. Verify the accuracy of the transducer reading with a minimum of two gauges.

Note: Manual calibration is available on Hand Held version V2.40 or greater.

Press ESC to return to SENSOR SETUP MENU.

P/N 374511B

Page 11

CONFIG MENU

1-SET THE CLOCK

2-SENSOR SETUP

3-PROTOCOL SETUP

4-COMM SETUP

5-LIGHT CONTROL

6-TEMP CONTROL

SENSOR SETUP MENU

1-PRESSURE #1

2-PRESSURE #2

3-TEMP #1

4-TEMP #2

5-TEMP #3

PRESSURE #1

HI ALARM

40

 

PSI

LO ALARM

20

 

PSI

XDCR RANGE

- 100

 

PSI

OFFSET

0

 

PSI

970307

HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 (Printed in U.S.A.)