Hand Held Device | PROTOCOL™ |
| |
CONFIG MENU (continued) |
|
2- SENSOR SETUP
Press 2 on the Keypad to enter the Sensor Setup Submenu. This screen has 6 menus.
1- PRESSURE #1
Press 1 on the Keypad to enter the Pressure #1 Submenu.
PRESSURE #1 controls the suction pressure for the Protocol Control. Press the CLR key. Key in the applicable suction pressure in psig for HI ALARM and press ENT. Repeat for LO ALARM.
Pressure Transducers are supplied in one of three ranges:
0 to 100
0 to 200
0 to 500
Using the key, toggle to the range of the transducer used. Press ENT.
Offset allows manual calibration for the pressure transducer. Manual calibration is achieved by entering a number between
WARNING: Improper calibration of the transducer could lead to unpredictable operation of the control. Verify the accuracy of the transducer reading with a minimum of two gauges.
Note: Manual calibration is available on Hand Held version V2.40 or greater.
Press ESC to return to SENSOR SETUP MENU.
P/N 374511B
Page 11
CONFIG MENU
SENSOR SETUP MENU
PRESSURE #1
HI ALARM | 40 |
| PSI |
LO ALARM | 20 |
| PSI |
XDCR RANGE | - 100 |
| PSI |
OFFSET | 0 |
| PSI |
970307 | HUSSMANN CORPORATION • BRIDGETON, MO |