Hand Held Device | PROTOCOL™ |
|
STATUS MENU (Continued)
T1 temperature reading for suction pressure reset or optional temperature input.
T2 temperature reading for satellite or optional temperature input.
T3 If split suction is installed, T3 may be factory set to read head pressure instead of temperature. Screen will show T3- ___PSI.
If split suction is not installed, T3 is a designated temperature input; but if you prefer, it can be configured as a pressure input (See page12).
Press ESC Key.
A7 thru A12 are additional temperature inputs. These readings may be established by the user as either ANALOG or DIGITAL under the CONFIGURATION MENU. When set on DIGITAL the read out will be either OPEN or CLOSED. The digital setting is applicable to thermostats or auxiliary contactors.
When the ANALOG setting is used a thermistor is used to retrieve temperature readings between – 40 and + 120˚F.
When not used the menu will read OPEN if set on DIGITAL. Set on ANALOG, an unused input will produce a – 40.
Press ESC Key.
COMPRESSOR RUN METER submenu appears. This menu shows the total number of hours that each compressor has been operating.
Press ESC to return to STATUS MENU.
P/N 374511B
Page 9
| TEMPERATURE MENU | |
| F | SP |
T1 - | - 40 | 0 |
T2 - | - 40 | 0 |
T3 - | - 40 | 0 |
| PRESS ENT FOR MORE | |
|
|
|
| TEMPERATURE MENU | |
| F | SP |
T4 - | 0 | 0 |
T5 - | 0 | 0 |
T6 - | 0 | 0 |
T7 - | 0 | 0 |
T8 | 0 | 0 |
| PRESS ENT FOR MORE | |
|
|
|
| AUXILIARY MENU |
A7 - | OPEN |
A8 - | CLOSED |
A9 - | OPEN |
A10 - | - 40 |
A11 - | 60 |
A12 - | - 40 |
|
|
COMPRESSOR RUN METER
COMP1 | 56 | HOURS |
COMP2 | 57 | HOURS |
COMP3 | 56 | HOURS |
COMP4 | 55 | HOURS |
COMP5 | 0 | HOURS |
COMP6 | 0 | HOURS |