P/N 374511B
Page 12
CONFIG MENU (continued)
2- PRESSURE #2
PROTOCOL™ | Hand Held Device |
|
Press 2 on the Keypad to enter the Pressure #2 Submenu.
PRESSURE #2 controls the suction pressure or Split Suction on the Protocol Control. Press the CLR key. Key in the applicable suction pressure in psig for HI ALARM and press ENT. Repeat for LO ALARM.
Pressure Transducers are supplied in one of three ranges:
SENSOR SETUP MENU
|
| 0 to 100 |
| PRESSURE #2 |
| |||
|
|
|
|
|
| |||
|
| 0 to 200 |
| HI ALARM | 0 | PSI | ||
|
| 0 to 500 |
| |||||
|
|
| LO ALARM | 0 | PSI | |||
|
|
|
|
|
| |||
Using the |
| key, toggle to the range of the trans- | XDCR RANGE | - 100 | PSI | |||
| ||||||||
ducer used. Press ENT. |
| ALARM | ENABLED |
| ||||
Using the |
| key, move down to the Alarm status | OFFSET | 0 | PSI | |||
|
|
|
| |||||
|
|
|
| |||||
selection. | Using the |
|
| key, toggle ENABLED or |
|
|
| |
DISABLED. |
| Press ENT. |
|
|
|
|
Offset allows manual calibration for the pressure transducer. Manual calibration is achieved by entering a number between
WARNING: Improper calibration of the transducer could lead to unpredictable operation of the control. Verify the accuracy of the transducer reading with a minimum of two gauges.
Note: Manual calibration is available on Hand
Held version V2.40 or greater.
Press ESC to return to SENSOR SETUP MENU.
HUSSMANN CORPORATION • BRIDGETON, MO | 970307 |