Page 18 | PROTOCOL™ |
|
|
|
| Hand Held Device | |||||||||
P/N 374511B |
|
|
|
|
|
| |||||||||
CONFIG MENU (continued) |
|
|
|
|
|
|
|
|
|
|
|
| |||
2- DEFR SETUP |
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
| PROTOCOL SETUP |
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Press | 2 on the Keypad to enter the Defrost Setup |
|
|
|
|
|
|
|
|
|
|
| |||
Submenu. |
|
|
|
|
|
|
|
|
|
| |||||
This screen programs the Control Board for the |
|
|
|
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
|
|
| |||||||
defrost parameters: |
|
|
|
|
|
|
|
|
|
| |||||
|
|
| Number of defrost circuits controlled |
|
|
|
|
|
|
|
|
|
|
| |
|
|
| Interlock status— |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
| ENABLED/DISABLED |
|
|
|
|
|
|
|
|
|
|
|
|
To change numeric fields, press the | CLR key. |
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
| CONFIG - DEFROST |
| |||||||||
Key in the applicable number. Press ENT. Use |
|
|
|
|
|
| |||||||||
|
|
|
|
|
|
|
|
|
|
| |||||
the |
|
| key, toggle between ENABLED/DISABLED. |
|
|
|
|
| # OF CIRCUITS | – | 7 |
|
| ||
|
|
|
|
|
|
|
| ||||||||
Press ENT. |
|
|
|
|
|
|
|
| |||||||
|
| * |
| INTERLOCK | – DISABLED |
| |||||||||
|
|
|
|
|
|
|
| ||||||||
Press ESC to return to PROTOCOL SETUP MENU. |
|
| DRIP CYCLE | – | 0 |
|
| ||||||||
|
|
|
|
|
|
| |||||||||
Interlock is used when there is only one defrost |
|
|
|
|
|
|
|
|
|
|
| ||||
circuit programmed into the control. If that one |
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
| |||||
defrost circuit is electric, all compressors will turn |
|
|
|
|
|
|
|
|
|
|
| ||||
on during the duration of the defrost. If the single | * This drip cycle is only used for reverse cycle gas | ||||||||||||||
defrost circuit is gas, the reverse cycle algorithm | defrost units. |
|
|
|
|
| |||||||||
will be activated. |
|
|
|
|
|
|
|
|
|
|
|
|