Infinity L30, M30 manual Program and Operate Three Stage Program Figure

Models: M30 L30

1 32
Download 32 pages 58.1 Kb
Page 12
Image 12

OPERATION

PROGRAM AND OPERATE - THREE STAGE PROGRAM (Figure 1)

1.Follow Two Stage Program, Steps 1 - 4.

2.Press ENTER / REVIEW. STAGE 2 light turns off, STAGE 3 and HEAT RATE lights turn on. Main Display shows four heat rate choices. Choose one:

A. Select heat rate between 1°F - 30°F /min (1°C - 17°C /min) using

.

B. Select "FULL" to program maximum heat rate.

 

C. Select "COOL" to program the furnace to cool to a selected temperature.

D. Select "NO" to turn of STAGE 3 and 4. This will result in a Two Stage Program.

NOTE: The HEAT RATE cannot be programmed to "COOL" in STAGE 1 - only in STAGE 2, 3 or 4.

3. Press ENTER / REVIEW. HEAT RATE light turns off and TEMP light turns on. Enter

for the

temperature required: heating temperature up to a maximum of 2012°F (1100°C) or cooling

temperature down to a minimum of 100°F (38°C).

 

4. Press ENTER / REVIEW. TEMP light turns off and HOLD TIME light turns on. Enter

to program the

time needed to hold at the above temperature (0 - 4hrs.).

 

5.For three stages, the furnace must be programmed not to use STAGE 4. Follow these steps:

A. After completing Step 4, press ENTER / REVIEW. STAGE 3 light turns off, STAGE 4 and HEAT

RATE lights turn on.

B. Press . Main Display shows “....5,4,3,2,1, COOL, NO.” Select “NO” to program the

furnace not to use STAGE 4.

6.All necessary information for this program is now entered.

7.To run the program immediately, press START / STOP.

8.To delay the start of the program to be ready to cast at the pre-set time (see One Stage Program, Step 3), press NIGHT TIME (DELAY START).

NOTE: If NIGHT TIME (DELAY START) is pressed while a program is running, the time remaining for completion of the program will appear on the Main Display for 5 seconds.

11

Page 12
Image 12
Infinity L30, M30 manual Program and Operate Three Stage Program Figure