SUPERHEAT CHARGING METHOD -
PISTON INDOOR
1.Operate system until temperatures and pressures stabilize (mini- mum of 10 minutes).
2.Measure and record indoor wet bulb (WB) temperature using a sling psychrometer and the outdoor dry bulb (DB) temperature using a thermometer.
3.Measure and record the suction pressure at the suction service valve port.
4.Using charts located on the unit, note the superheat value corre- sponding to the intersection of the indoor wet bulb and the outdoor dry bulb.
5.With the superheat value obtained in step 4 and the suction pres- sure value from step 3, find the intersection of the values on the chart. This is the required suction tube temperature at the suction service valve.
6.To bring the tube temperature in line with the required value from chart, add refrigerant to the service port to cause the tube temper- ature to fall and reclaim refrigerant to cause the temperature to rise.
SUBCOOLING CHARGING METHOD - TXV INDOOR
The recommended subcooling is 10°F
1.Set the system running in the cooling mode by setting the thermo- stat at least 6°F below the room temperature.
2.Operate the system for a minimum of
3.Refer to the tabular data sheet for the recommended airflow and verify this indoor airflow (it should be about 400 SCFM per ton).
4.Measure the liquid refrigerant pressure P and temperature T at the service valve.
5.Calculate the saturated liquid temperature ST from Table 2.
6.Subcooling temperature TC = Saturated Temperature (ST) - Liquid Temp (T).
Example: The pressure P and temperature T measured at the liq- uid service port is 196 psig and 90°F, respectively. From Table 2, the saturated temperature for 196 psig is 100°F. The subcooling temperature TC =
Add charge if the calculated subcooling temperature TC in Step 6 is lower than the recommended level. Remove and recover the refrigerant if the subcooling TC is higher than the recommended level. See Table 2.
Check flare caps on service ports to be sure they are leak tight. DO NOT OVERTIGHTEN (between 40 and 60 inch - lbs. maximum).
TABLE 2: |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Pressure | Temp °F | Pressure | Temp °F | Pressure | Temp °F | Pressure | Temp °F |
| Pressure | Temp °F | Pressure | Temp °F | |||||
PSIG | PSIG | PSIG | PSIG |
| PSIG |
| PSIG | ||||||||||
|
|
|
|
|
|
|
|
|
|
|
| ||||||
80 | 48 |
| 110 | 64 |
| 140 | 78 | 170 | 91 | 200 | 101 | 230 | 111 | ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
82 | 49 |
| 112 | 65 |
| 142 | 79 | 172 | 91 | 202 | 102 | 232 | 112 | ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
84 | 50 |
| 114 | 66 |
| 144 | 80 | 174 | 92 | 204 | 103 | 234 | 112 | ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
86 | 51 |
| 116 | 67 |
| 146 | 81 | 176 | 93 | 206 | 103 | 236 | 113 | ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
88 | 52 |
| 118 | 68 |
| 148 | 82 | 178 | 94 | 208 | 104 | 238 | 114 | ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
90 | 54 |
| 120 | 69 |
| 150 | 83 | 180 | 94 | 210 | 105 | 240 | 114 | ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
92 | 55 |
| 122 | 70 |
| 152 | 84 | 182 | 95 | 212 | 105 | 242 | 115 | ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
94 | 56 |
| 124 | 71 |
| 154 | 84 | 184 | 96 | 214 | 106 | 244 | 115 | ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
96 | 57 |
| 126 | 72 |
| 156 | 85 | 186 | 97 | 216 | 107 | 246 | 116 | ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
98 | 58 |
| 128 | 73 |
| 158 | 86 | 188 | 97 | 218 | 107 | 248 | 117 | ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
100 | 59 |
| 130 | 74 |
| 160 | 87 | 190 | 98 | 220 | 108 | 250 | 117 | ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
102 | 60 |
| 132 | 75 |
| 162 | 88 | 192 | 99 | 222 | 109 | 252 | 118 | ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
104 | 61 |
| 134 | 76 |
| 164 | 88 | 194 | 99 | 224 | 109 | 254 | 118 | ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
106 | 62 |
| 136 | 77 |
| 166 | 89 | 196 | 100 | 226 | 110 | 256 | 119 | ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
108 | 63 |
| 138 | 78 |
| 168 | 90 | 198 | 101 | 228 | 111 | 258 | 119 | ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
IT IS UNLAWFUL TO KNOWINGLY VENT, RELEASE OR DIS- CHARGE REFRIGERANT INTO THE OPEN AIR DURING REPAIR, SERVICE, MAINTENANCE OR THE FINAL DISPOSAL OF THIS UNIT.
WHEN THE SYSTEM IS FUNCTIONING PROPERLY AND THE OWNER HAS BEEN FULLY INSTRUCTED, SECURE THE OWNER’S APPROVAL.
All field wiring must USE COPPER CONDUCTORS ONLY and be in accordance with Local, National, Fire, Safety & Electrical Codes. This unit must be grounded with a separate ground wire in accordance with the above codes.
The complete connection diagram and schematic wiring label is located on the inside surface of the unit service access panel.
SECTION VIII: ELECTRICAL
CONNECTIONS
GENERAL INFORMATION & GROUNDING
Check the electrical supply to be sure that it meets the values specified on the unit nameplate and wiring label.
Power wiring, control (low voltage) wiring, disconnect switches and over current protection must be supplied by the installer. Wire size should be sized per NEC requirements.
FIELD CONNECTIONS POWER WIRING
1.Install the proper size weatherproof disconnect switch outdoors and within sight of the unit.
2.Remove the screws at the top and sides of the corner cover. Slide corner cover down and remove from unit.
3.Run power wiring from the disconnect switch to the unit.
4.Route wires from disconnect through power wiring opening pro- vided and into the unit control box as shown in Figure 6.
5.Install the proper size
6 | Johnson Controls Unitary Products |