Johnson Controls 13 SEER - GCGD installation manual Section Viii Electrical Connections

Models: 13 SEER - GCGD

1 16
Download 16 pages 12.47 Kb
Page 6
Image 6
SUPERHEAT CHARGING METHOD -

1031452-UIM-B-0513

SUPERHEAT CHARGING METHOD -

PISTON INDOOR

1.Operate system until temperatures and pressures stabilize (mini- mum of 10 minutes).

2.Measure and record indoor wet bulb (WB) temperature using a sling psychrometer and the outdoor dry bulb (DB) temperature using a thermometer.

3.Measure and record the suction pressure at the suction service valve port.

4.Using charts located on the unit, note the superheat value corre- sponding to the intersection of the indoor wet bulb and the outdoor dry bulb.

5.With the superheat value obtained in step 4 and the suction pres- sure value from step 3, find the intersection of the values on the chart. This is the required suction tube temperature at the suction service valve.

6.To bring the tube temperature in line with the required value from chart, add refrigerant to the service port to cause the tube temper- ature to fall and reclaim refrigerant to cause the temperature to rise.

SUBCOOLING CHARGING METHOD - TXV INDOOR

The recommended subcooling is 10°F

1.Set the system running in the cooling mode by setting the thermo- stat at least 6°F below the room temperature.

2.Operate the system for a minimum of 15-20 minutes.

3.Refer to the tabular data sheet for the recommended airflow and verify this indoor airflow (it should be about 400 SCFM per ton).

4.Measure the liquid refrigerant pressure P and temperature T at the service valve.

5.Calculate the saturated liquid temperature ST from Table 2.

6.Subcooling temperature TC = Saturated Temperature (ST) - Liquid Temp (T).

Example: The pressure P and temperature T measured at the liq- uid service port is 196 psig and 90°F, respectively. From Table 2, the saturated temperature for 196 psig is 100°F. The subcooling temperature TC = 100°-90°=10°F

Add charge if the calculated subcooling temperature TC in Step 6 is lower than the recommended level. Remove and recover the refrigerant if the subcooling TC is higher than the recommended level. See Table 2.

Check flare caps on service ports to be sure they are leak tight. DO NOT OVERTIGHTEN (between 40 and 60 inch - lbs. maximum).

TABLE 2: R-22 Saturated Properties

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pressure

Temp °F

Pressure

Temp °F

Pressure

Temp °F

Pressure

Temp °F

 

Pressure

Temp °F

Pressure

Temp °F

PSIG

PSIG

PSIG

PSIG

 

PSIG

 

PSIG

 

 

 

 

 

 

 

 

 

 

 

 

80

48

 

110

64

 

140

78

170

91

200

101

230

111

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

82

49

 

112

65

 

142

79

172

91

202

102

232

112

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

84

50

 

114

66

 

144

80

174

92

204

103

234

112

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

86

51

 

116

67

 

146

81

176

93

206

103

236

113

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

88

52

 

118

68

 

148

82

178

94

208

104

238

114

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

90

54

 

120

69

 

150

83

180

94

210

105

240

114

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

92

55

 

122

70

 

152

84

182

95

212

105

242

115

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

94

56

 

124

71

 

154

84

184

96

214

106

244

115

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

96

57

 

126

72

 

156

85

186

97

216

107

246

116

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

98

58

 

128

73

 

158

86

188

97

218

107

248

117

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

100

59

 

130

74

 

160

87

190

98

220

108

250

117

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

102

60

 

132

75

 

162

88

192

99

222

109

252

118

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

104

61

 

134

76

 

164

88

194

99

224

109

254

118

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

106

62

 

136

77

 

166

89

196

100

226

110

256

119

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

108

63

 

138

78

 

168

90

198

101

228

111

258

119

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IT IS UNLAWFUL TO KNOWINGLY VENT, RELEASE OR DIS- CHARGE REFRIGERANT INTO THE OPEN AIR DURING REPAIR, SERVICE, MAINTENANCE OR THE FINAL DISPOSAL OF THIS UNIT.

WHEN THE SYSTEM IS FUNCTIONING PROPERLY AND THE OWNER HAS BEEN FULLY INSTRUCTED, SECURE THE OWNER’S APPROVAL.

All field wiring must USE COPPER CONDUCTORS ONLY and be in accordance with Local, National, Fire, Safety & Electrical Codes. This unit must be grounded with a separate ground wire in accordance with the above codes.

The complete connection diagram and schematic wiring label is located on the inside surface of the unit service access panel.

SECTION VIII: ELECTRICAL

CONNECTIONS

GENERAL INFORMATION & GROUNDING

Check the electrical supply to be sure that it meets the values specified on the unit nameplate and wiring label.

Power wiring, control (low voltage) wiring, disconnect switches and over current protection must be supplied by the installer. Wire size should be sized per NEC requirements.

FIELD CONNECTIONS POWER WIRING

1.Install the proper size weatherproof disconnect switch outdoors and within sight of the unit.

2.Remove the screws at the top and sides of the corner cover. Slide corner cover down and remove from unit.

3.Run power wiring from the disconnect switch to the unit.

4.Route wires from disconnect through power wiring opening pro- vided and into the unit control box as shown in Figure 6.

5.Install the proper size time-delay fuses or circuit breaker, and make the power supply connections.

6

Johnson Controls Unitary Products

Page 6
Image 6
Johnson Controls 13 SEER - GCGD Section Viii Electrical Connections, Superheat Charging Method Piston Indoor