Johnson Controls GG9S*MP, TG9S*MP installation manual Combustion Air Supply, Outdoor Combustion Air

Models: TG9S*MP GG9S*MP

1 38
Download 38 pages 7.38 Kb
Page 25
Image 25
COMBUSTION AIR SUPPLY

364861-UIM-B-0708

COMBUSTION AIR SUPPLY

All installations must comply with Section 5.3, Air for Combustion and Ventilation of the National Fuel Gas Code, ANSI Z223.1 or Sections 7.2, 7.3 or 7.4 of CAN/CGA B149.1 or .2 Installation Code - latest edi- tions.

This furnace is certified to be installed with one of three possible com- bustion air intake configurations.

1. OUTDOOR COMBUSTION AIR: This is a direct vent configuration

where the combustion air is supplied through a PVC or ABS pipe

that is connected to the PVC coupling attached to the furnace and

is terminated in the same atmospheric zone as the vent. This type

of installation is approved on all models. Refer to Figure 36.

2. AMBIENT COMBUSTION AIR: Combustion air is supplied from

the area surrounding the furnace through openings in the furnace

casing. The combustion air and the vent pipes are not terminated

in the same atmospheric zone. Refer to Figure 21 for vent termina-

tions. Refer to "Ambient Combustion Air Supply" for proper instal-

COMBUSTION AIR

Vent pipe cements into socket just above top panel

Outdoor Combustion Air Or vent pipe may be clamped into outlet of drain coupling

lation. Refer to Figure 36.

3. VENTILATED COMBUSTION AIR: Combustion air is supplied

through a PVC or ABS pipe that is connected to the PVC coupling

attached to the burner box and is terminated in a ventilated attic or

crawl space. The combustion air and the vent pipes are not termi-

nated in the same atmospheric zone. Refer to Figure 37 for attic

and crawl space termination. Only the combustion air intake may

terminate in the attic. The vent must terminate outside.

Outdoor Combustion Air

Combustion Air Intake/Vent Connections

This installation requires combustion air to be brought in from outdoors. This requires a properly sized pipe (Shown in Figure 30) that will bring air in from the outdoors to the furnace combustion air intake collar on the burner box. The second pipe (Shown in Figure 30) is the furnace vent pipe.

FIGURE 35: Combustion Airflow Path Through The Furnace Casing

This type of installation requires that the supply air to the appli- ance(s) be of a sufficient amount to support all of the appliance(s) in the area. Operation of a mechanical exhaust, such as an exhaust fan, kitchen ventilation system, clothes dryer or fireplace may cre- ate conditions requiring special attention to avoid unsatisfactory operation of gas appliances. A venting problem or a lack of supply air will result in a hazardous condition, which can cause the appli- ance to soot and generate dangerous levels of CARBON MONOX- IDE, which can lead to serious injury, property damage and / or death.

An unconfined space is not less than 50 cu.ft (1.42 m3) per 1,000 Btu/ hr (0.2928 kW) input rating for all of the appliances installed in that area.

Connects to collar on top of burner box

Vent pipe cements into socket just above top panel

Or vent pipe may be clamped into outlet of drain coupling

Rooms communicating directly with the space containing the appli- ances are considered part of the unconfined space, if doors are fur- nished with openings or louvers.

A confined space is an area with less than 50 cu.ft (1.42 m3) per 1,000 Btu/hr (0.2928 kW) input rating for all of the appliances installed in that area. The following must be considered to obtain proper air for combus- tion and ventilation in confined spaces.

Combustion Air Source From Outdoors

The blocking effects of louvers, grilles and screens must be given con- sideration in calculating free area. If the free area of a specific louver or grille is not known, refer to Table 11, to estimate free area.

Table 11: Estimated Free Area

FIGURE 34: Direct Vent Air Intake Connection and Vent Connection

The combustion air intake pipe should be located either through the wall (horizontal or side vent) or through the roof (vertical vent). Care should be taken to locate side vented systems where trees or shrubs will not block or restrict supply air from entering the terminal.

Also, the terminal assembly should be located as far as possible from a swimming pool or a location where swimming pool chemicals might be stored. Be sure the terminal assembly follows the outdoor clearances listed in Section #1 “Outdoor Air Contaminants.”

Ambient Combustion Air Supply

This type installation will draw the air required for combustion from within the space surrounding the appliance and from areas or rooms adjacent to the space surrounding the appliance. This may be from within the space in a non-confined location or it may be brought into the furnace area from outdoors through permanent openings or ducts. It is not piped directly into the furnace. A single, properly sized pipe from the furnace vent connector to the outdoors must be provided. It is recom- mended that the supplied intake coupling & 18” of pipe be attached to the furnace to prevent accidental blockage of the combustion air intake.

Wood or Metal

Wood 20-25%*

Louvers or Grilles

Metal 60-70% *

 

 

Screens+

1/4” (0.635 cm)

mesh or larger 100%

 

 

 

* Do not use less than 1/4”(0.635 cm) mesh

+Free area of louvers and grille varies widely; the installer should follow louver or grille manufacturer’s instructions.

Dampers, Louvers and Grilles (Canada Only)

1.The free area of a supply air opening shall be calculated by sub- tracting the blockage area of all fixed louvers grilles or screens from the gross area of the opening.

2.Apertures in a fixed louver, a grille, or screen shall have no dimen- sion smaller than 0.25” (0.64 cm).

3.A manually operated damper or manually adjustable louvers are not permitted for use.

4.A automatically operated damper or automatically adjustable lou- vers shall be interlocked so that the main burner cannot operate unless either the damper or the louver is in the fully open position.

Johnson Controls Unitary Products

25

Page 25
Image 25
Johnson Controls GG9S*MP, TG9S*MP Combustion Air Supply, Outdoor Combustion Air, Combustion Air Source From Outdoors