Johnson Controls TG9S*MP Coil Flange Installation, Furnace Assembly - Mc Series Coils Only

Models: TG9S*MP GG9S*MP

1 38
Download 38 pages 7.38 Kb
Page 6
Image 6
COIL FLANGE INSTALLATION

364861-UIM-B-0708

COIL FLANGE INSTALLATION

The coils include removable flanges to allow proper fit up with furnaces having various inlet and outlet flange configurations. The two flanges are attached to the top of the coil in the factory during production. For proper configuration of flanges refer to Figure 3, "Coil Flange".

Do not drill any holes or drive any screws into the front duct flange on the coil in order to prevent damaging coil tubing. See Figure 6, "PC Series Upflow Coil Installation"

ALTERNATE FLANGE LOCATION (Used for downflow or horizontal left installations)

FACTORY

FLANGE

LOCATION

(Used for upflow

or horizontal

right installations)

C

D(Min)

 

Flexible

 

Duct Collar

Field

 

Fabricated

 

Ductwork

Do not drill

 

or Screw

Upflow

this flange

Coil

 

Upflow

 

Furnace

 

FIGURE 3: Coil Flange

FURNACE ASSEMBLY - MC SERIES COILS ONLY

MC coils are supplied ready to be installed in a horizontal position. A horizontal pan is factory installed. MC coils should be installed in all hor- izontal applications with the horizontal drain pan side down.

FURNACE ASSEMBLY - MC SERIES COILS ONLYMounting Plate

Furnace

FIGURE 4: Horizontal Right Application

For horizontal left hand applications no conversion is required to an MC coil when used with a downflow/horizontal furnace. A mounting plate, supplied with every coil should always be installed on the side desig- nated as top side. See Figures 4 & 5.

Mounting PlateFURNACE ASSEMBLY - PC SERIES COILS

Furnace

FIGURE 5: Horizontal Left Application

FURNACE ASSEMBLY - PC SERIES COILS

These upflow coils are designed for installation on top of upflow fur- naces only.

If the coil is used with a furnace of a different size, use a 45° transition to allow proper air distribution through the coil.

1.Position the coil casing over the furnace opening as shown in Fig- ure 6, "PC Series Upflow Coil Installation".

2.Place the ductwork over the coil casing flange and secure.

3.Check for air leakage between the furnace and coil casing and seal appropriately.

Primary

Secondary

Alternate

Drain

Drain Location

Drain

 

 

FIGURE 6: PC Series Upflow Coil Installation

Table 2: Coil Projection Dimensions - PC Series Coils

COIL SIZE

DIMENSION “C” INCH

PC18

3-1/2

PC24

4-1/2

PC30, PC32, PC35

4-1/2

PC42, PC43, PC36, PC37

5-1/2

PC48

6-1/2

PC60

9

NOTE: Dimension “C” should be at least 2/3 of dimension “D”. See Fig- ure 6, "PC Series Upflow Coil Installation"

CRITICAL COIL PROJECTION

The coil assembly must be located in the duct such that a minimum dis- tance is maintained between the top of the coil and the top of the duct. Refer to Table 6.

COIL / FURNACE ASSEMBLY - HC SERIES COILS

These coils are supplied ready to be installed in a right hand position or a left hand position. When used in conjunction with a horizontal furnace (blow through) application, the coil should be oriented with the opening of the “A” coil closest to the furnace. See Figure 6.

NOTE: Each coil is shipped with an external tie plate that should be used to secure the coil to the furnace. It should be installed on the back side of the coil using the dimpled pilot holes. See Figure 6.

Use tie plate

supplied with coil

Gas Furnace

FIGURE 7: Horizontal Left or Right application (Right Shown)

6

Johnson Controls Unitary Products

Page 6
Image 6
Johnson Controls TG9S*MP Coil Flange Installation, Furnace Assembly - Mc Series Coils Only, Critical Coil Projection