Johnson Controls TGLS*MP Section V Electrical Power, Electrical Power Connections, UIM-G-1211

Models: TG8S*MP GG8S*MP TGLS*MP GGLS*MP

1 30
Download 30 pages 59.22 Kb
Page 12
Image 12
SECTION V: ELECTRICAL POWER

356485-UIM-G-1211

SECTION V: ELECTRICAL POWER

ELECTRICAL POWER CONNECTIONS

Field wiring to the unit must be grounded. Electric wires that are field installed shall conform to the temperature limitation for 63°F (35°C) rise wire when installed in accordance with instructions. Refer to Table 6 in these instructions for specific furnace electrical data.

Table 6: Ratings & Physical / Electrical Data

Use copper conductors only.

 

 

 

 

Nominal

 

Air Temp.

Max.

 

 

 

 

 

 

Input

Output

 

Outlet

Blower

 

Max

Total

Min. wire Size

Airflow

AFU

Rise

Blower

 

 

 

 

Air Temp

 

 

Over-Current

Unit

(awg) @ 75 ft

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E

 

 

 

 

 

 

Size

Protect

Amps

one way

MB

kW

MB

kW

CFM

m3/

°F

°C

°F

°C

HP

Amp

 

 

H

H

min

 

s

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40

11.7

32

9.4

800

22.7

80.0

25-55

14-31

155

68.3

1/5

2.1

9 x 8

10

4.5

14

60

17.6

48

14.1

1000

28.3

80.0

25-55

14-31

155

68.3

1/3

3.8

9 x 8

10

6.0

14

60

17.6

48

14.1

1200

34.0

80.0

30-60

17-33

170

76.7

1/3

4.8

11 x 8

10

7.0

14

80

23.5

64

18.8

1200

34.0

80.0

35-65

19-36

165

73.9

1/3

4.8

11 x 8

10

7.5

14

80

23.5

64

18.8

1600

45.3

80.0

25-55

14-31

155

68.3

1/2

7.5

11 x 10

15

10.0

14

80

23.5

64

18.8

2200

62.3

80.0

25-55

14-31

155

68.3

1

14.5

11 x 11

20

16.0

12

100

29.3

80

23.4

1200

34.0

80.0

40-70

22-39

170

76.7

1/3

4.8

9 x 8

10

7.5

14

100

29.3

80

23.4

1600

45.3

80.0

35-65

19-36

165

73.9

1/2

7.5

11 x 10

15

10.0

14

100

29.3

80

23.4

2000

56.6

80.0

25-55

14-31

155

68.3

1

14.5

11 x 11

20

17.0

12

120

33.7

96

26.9

1600

45.3

80.0

40-70

22-39

170

76.7

1/2

7.5

11 x 10

15

10.0

14

120

33.7

96

26.9

2000

56.6

80.0

30-60

17-33

160

71.1

1

14.5

11 x 11

20

17.0

12

130

38.1

104

30.5

2000

56.6

80.0

35-65

19-36

165

73.9

1

14.5

11 x 11

20

17.0

12

Annual Fuel Utilization Efficiency (AFUE) numbers are determined in accordance with DOE Test procedures.

Wire size and over current protection must comply with the National Electrical Code (NFPA-70-latest edition) and all local codes. The furnace shall be installed so that the electrical components are protected from water.

SUPPLY VOLTAGE CONNECTIONS

Junction Box

Connect ground lead to screw

Electrical Entry ELECTRICAL POWER CONNECTIONS

L1-Hot BLK

Neutral WHT

FIGURE 16: Electrical Wiring

1.Provide a power supply separate from all other circuits. Install overcurrent protection and disconnect switch per local/national electrical codes. The switch should be close to the unit for conve- nience in servicing. With the disconnect or fused switch in the OFF position, check all wiring against the unit wiring label. Refer to the wiring diagram in this instruction.

2.Remove the screws retaining the wiring box cover. Route the power wiring through the opening in the unit into the junction box with a conduit connector or other proper connection. In the junc- tion box there will be 3 wires, a Black Wire, a White Wire. Connect the power supply as shown on the unit-wiring label on the inside of the blower compartment door or the wiring schematic in this sec- tion. The black furnace lead must be connected to the L1 (hot) wire from the power supply. The white furnace screw must be con- nected to neutral. Connect the power supply ground to the green screw (equipment ground) An alternate wiring method is to use a field provided 2” (5.1 cm) x 4” (10.2 cm) box and cover on the out- side of the furnace. Route the furnace leads into the box using a protective bushing where the wires pass through the furnace panel. After making the wiring connections replace the wiring box cover and screws. Refer to Figure 16.

3.The furnace's control system requires correct polarity of the power supply and a proper ground connection. Refer to Figure 16

The power connection leads and wiring box may be relocated to the left side of the furnace. Remove the screws and cut wire tie holding excess wiring. Reposition on the left side of the furnace and fasten using holes provided.

LOW VOLTAGE CONTROL WIRING CONNECTIONS

Install the field-supplied thermostat by following the instructions that come with the thermostat. With the thermostat set in the OFF position and the main electrical source disconnected, connect the thermostat wiring from the wiring connections on the thermostat to the terminal board on the ignition module, as shown in Figures 17 or 18. Electronic thermostats may require the common wire to be connected. Apply strain relief to thermostat wires passing through cabinet. If air condition- ing equipment is installed, use thermostat wiring to connect the Y and C terminals on the furnace control board to the proper wires on the con- densing unit (unit outside).

Set the heat anticipator in the room thermostat to 0.4 amps. Setting it lower will cause short cycles. Setting it higher will cause the room temperature to exceed the set points.

Some electronic thermostats do not have adjustable heat anticipa- tors. They should be set to six cycles per hour. Follow the thermo- stat manufacturer's instructions.

The 24-volt, 40 VA transformer is sized for the furnace components only, and should not be connected to power auxiliary devices such as humidifiers, air cleaners, etc. The transformer may provide power for an air conditioning unit contactor.

12

Johnson Controls Unitary Products

Page 12
Image 12
Johnson Controls TGLS*MP Section V Electrical Power, Electrical Power Connections, Supply Voltage Connections, UIM-G-1211