![Single-Wire Twinning Operation](/images/new-backgrounds/47899/4789931x1.webp)
Single-Wire Twinning Operation
Heating - On a call for heat (W signal) from the wall thermostat, both furnaces will start the ignition sequence and the burners on both fur- naces will light. About thirty seconds after the burners light, the blowers on both furnaces will come on in heating speed. When the thermostat is satisfied, the burners will all shut off and, after the selected blower off delay time, both blowers will shut off at the same time. The twinning control ensures that both blowers come on and shut off at the same time.
Cooling - On a call for cooling (Y signal) from the wall thermostat, both furnace blowers will come on at the same time in cooling speed. When the thermostat is satisfied, both blowers will stay on for 60 seconds, then will shut off at the same time.
Continuous Fan - On a thermostat call for continuous fan (G signal), both furnace blowers will come on at the same time in cooling speed and will stay on until the G signal is removed.
FURNACE 1 | FURNACE 2 |
CONTROL BOARD | CONTROL BOARD |
Single-Wire Staging Operation
Heating - On a call for
Cooling - On a call for cooling (Y signal) from the wall thermostat, both furnace blowers will come on at the same time. When the thermostat is satisfied, both blowers will stay on for 60 seconds, then will shut off at the same time.
Continuous Fan - On a thermostat call for continuous fan (G signal), both furnace blowers will come on at the same time in cooling speed and will stay on until the G signal is removed.
W |
G |
W G
FURNACE 1 | FURNACE 2 |
CONTROL BOARD | CONTROL BOARD |
C |
|
R | TWIN |
Y | ISOLATION |
| RELAY |
C
R TWIN Y
W |
|
G |
|
C |
|
R | TWIN |
Y | ISOLATION |
| |
| RELAY |
W
G
C
R TWIN Y
|
|
|
|
|
TO A/C |
| W G R Y |
| |
| WALL THERMOSTAT |
FIGURE 20: Single Wire Twinning Wiring Diagram
STAGING
This control can also be used along with a
Single-Wire Staging
The
Single-Wire Staging Instructions
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
TO A/C |
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
| ||||
|
| W1 G R Y W2 |
| ||||||||||
|
|
|
|
| WALL THERMOSTAT |
|
FIGURE 21: Single Wire Staging Wiring Diagram
SECTION VII: VENT SYSTEM
VENT CONNECTIONS
All models are provided with a flue transition that is sized for 4” diame- ter vent connections. If a larger size vent connector is required, that connection must be installed external to the furnace. Figure 22 shows the furnace as it is shipped from the factory. To convert to a horizontal or downflow position, remove the four screws that secure the inducer assembly and rotate 90° being careful not to damage the gasket. Rein- stall screws. Remove cap from appropriate vent outlet location on the cabinet, cut insulation in cabinet to same size as the hole provided and reinstall cap in the hole in the top panel.
In downflow applications, do not block the combustion air inlet. The furnace must be installed on a coil cabinet or subbase to allow com- bustion air to enter the burner compartment.
Connect the control wiring as shown in Figure 22.
1.Connect the low voltage wiring from the wall thermostat to the ter- minal strip on the control board of Furnace #1. For staging applica- tions, the wire from thermostat W1 is connected to the W connection on the board on Furnace #1. The wire from thermostat W2 is connected to Furnace #2 through a separate relay, as described below.
2.Connect a wire from the TWIN terminal of Furnace #1 to the TWIN terminal of Furnace #2.
3.Install a separate 24V relay as shown in the diagram below. Use of this relay is required, as it ensures that the transformers of the two furnaces are isolated, thus preventing the possibility of any safety devices being bypassed.
4.Connect the common between furnace #1 and furnace #2.
COMBUSTION AIR INDUCER
90° | Mounting Screw | 90° |
| (Remove) |
|
Pressure Switch |
|
Tube Routing | Flue Transition |
| (Do Not Remove) |
Pressure
Switch
Mounting Screw (Remove)
FIGURE 22: Combustion Air Inducer
16 | Johnson Controls Unitary Products |