Co-linear Vent Installation
The GF 300 DV may be vented through a masonry or Class A prefabricated chimney using a
These installation requirements must be followed:
1.Use the guidelines for
| #991 High |
Exhaust Gas | Wind Cap |
|
Intake Air
Max.
Min.
1.Prior to the installation the chimney flue must be thoroughly cleaned and inspected by a qualified chimney service person.
2.In a masonry chimney, a fireclay liner must be present the entire length of the chimney.
3.Prefabricated chimneys must be UL 103 or ULC
4.No appliance can be installed into a chimney flue serving any other appliance of any kind.
5.THE AIR INTAKE FLEX PIPE MUST EXTEND 6 FEET BEYOND THE DAMPER AREA OF THE FIREPLACE.
6.If the intake flex duct does not extend the full length of the chimney and connect to both the unit and the termination cap, A METAL BLOCK OFF PLATE MUST BE CONSTRUCTED AND INSTALLED ABOVE THE UNIT PRIOR TO THE END OF THE INTAKE FLEX AND MUST COMPLETELY SEAL THE CHIMNEY FLUE FROM THE ROOM.
The chimney |
|
must be sealed | Dual 3”Flex |
off from the | Liners |
room by a steel |
|
plate at the |
|
damper area. |
|
Max. offset 24” (609 mm)
The Air
Intake Flex pipe must extend 6 feet beyond the damper.
Consult with the local code authority having juris- diction before proceeding with this type of installation.
Refer to the vent manufacturer’s instructions for specific installation requirements.
WARNING: FAILURE TO POSITION THE PARTS AND STOVE IN ACCORDANCE WITH THESE DIAGRAMS OR FAILURE TO USE ONLY PARTS SPECIFICALLY APPROVED FOR USE WITH THIS APPLIANCE MAY RESULT IN PROP- ERTY DAMAGE OR PERSONAL INJURY. BE SURE TO MAINTAIN THE PROPER CLEARANCES TO COMBUSTIBLES AS DEFINED IN THIS MANUAL AND IN THE INSTRUC- TIONS PROVIDED WITH EACH VENT COMPONENT.
Figure 14.
28 3/4” to top of 25”
to center Adapter. of flue
collar
Figure 15. Simpson